Wiring
Xenus XSL User Guide
62
Copley Controls Corp.
4.2: AC Mains (J1)
Mating Connector
Description
Euro-style, 4 position, 7.5 mm pluggable female terminal block.
Manufacturer PN
Wago Standard 721-204/026-045; Right Angle 732-180/026-000
Wire size
22 - 12 AWG
Recommended Wire
12 AWG, 600 V
Wire Insertion/Extraction Tool
Wago 231-131
Standard connector and tool are included in connector kit XSL-CK or XSL-CA
Pin Description
Pin Signal
Function
1
L1
AC power input (hot or L1)
2
L2
AC power input (neutral or L2)
3
Protective ground
Chassis safety ground
4
L3
AC power input (L3)
AC Mains Fuse Recommendation
Recommended fuse type: Class CC, 600 Vac rated, Ferraz-Shawmut ATDR, Littelfuse CCMR,
Bussman LP-CC, or equivalent.
AC Mains Wiring Diagram (Single-Phase)
Amplifier
L1
L2
Fuses**
L1 (Line)
L2 (Neut)
Earth
Ground
Keep wire length
as short as
possible. Not to
exceed 1 Meter.
1
Ø
47-63 Hz
100-240 VAC
** Not required on
a neutral line.
J1-4
J1-1
J1-2
J1
* Filter Concepts SF20L
(or equivalent)
used for CE compliance
L
O
A
D
L
I
N
E
Line Filter*
AC Mains Wiring Diagram (Three-Phase)
A
C
B
Line Filter*
Fuses
L3
L2
Earth
Ground
3
Ø
47-63 Hz
100-240 VAC
Gnd
A
C
B
L1
L3
Keep wire length
as short as
possible. Not to
exceed 1 Meter.
Amplifier J1
L1
L2
J1-4
J1-1
J1-2
* Filter Concepts 3F15
(or equivalent)
used for CE compliance
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com