ServoTube Motor Setup
Xenus XSL User Guide
188
Copley Controls Corp.
G.1.3: Calculating ServoTube Initial Values
G.1.3.1
Click
Calculate
(
) to calculate and display initial loop gains and limits.
G.1.3.2
Load the values into volatile memory by clicking
OK
OR
to close the screen without saving changes, click
Cancel
.
G.1.3.3
Click
Save to Flash
(
).
G.1.4: Setting Up the Motor Over Temperature Input
It is important to program the amplifier to shut down the PWM outputs when a motor over
temperature signal is sent over digital input IN5 by the motor temperature sensor.
G.1.4.1
On the CME 2 Main screen, click
Input/Output
to display the
Input/Output
screen
.
G.1.4.2
Verify that the inputs group containing IN5 is pulled up to in5 V
and the IN5 function is set to
Motor Temp-HI Disables
.
If the motor temperature sensor is wired to IN5, and the motor temperature is within
specified operating range, a grey indicator will show that the input is inactive, and the
amplifier is not disabled by a motor over temperature fault.
G.1.5: Other ServoTube I/O and Fault Latching Setup Steps
Before proceeding with this chapter, perform any other required configuration of the amplifier’s
digital inputs, digital outputs and fault latching.
Inputs and outputs
Digital Inputs (p. 93)
Standard Digital Outputs (p. 95)
Custom Digital Outputs (p. 96)
Save Input/Output Changes (p. 96)
Fault latching
Fault Latching (p. 97)