Using CME 2
Xenus XSL User Guide
128
Copley Controls Corp.
6.2.4: Quick Copy Setup Procedure
Use this procedure to configure an amplifier/motor pair by copying a
.ccx
file that was prepared for
the amplifier/motor combination.
6.2.4.1
Make sure the amplifier is connected to the PC using the J5 RS-232 connector.
For wiring instructions, see
RS-232 Serial Communications (J5) (p. 66)
.
6.2.4.2
Start CME 2 by double-clicking the CME 2 shortcut icon on the Windows desktop:
6.2.4.3
On the
Main
screen, click
Restore amplifier data from disk
(
).
6.2.4.4
When prompted, navigate to the folder containing the appropriate
.ccx
file.
Highlight the file name and then click
Open
to load the file data into volatile memory.
6.2.4.5
On the
Main
screen, click
Save to Flash
(
) to commit the new settings to flash
memory.