Xenus Plus User Guide
16-01344 Rev 06
Copley Controls
158
E.1: Single-Axis and Multi-Drop
An XPL/XP2 drive’s RS-232 serial bus can be used by CME for drive commissioning. The serial bus
can also be used by an external control application (HMI, PLC, PC, etc.) for setup and direct serial
control of the drive. The control application can issue commands in ASCII format.
For experimentation and simple setup and control, a telnet device such as the standard Microsoft
Windows HyperTerminal can also be used to send commands in ASCII format. For more information,
see Copley Controls ASCII RS-232 User Guide.
The serially connected drive can also be used as a multi-drop gateway for access to other drives
linked in a series of CAN bus connections.
Instructions for hooking up a single-axis connection and a multi-drop network appear below.
E.1.2: Single-Axis Connections
For RS-232 serial bus control of a single axis, set the CAN node address of that axis drive to zero
(0). Note that if the CAN node address is switched to zero after power-up, the drive must be reset
or power cycled to make the new address setting take effect.
E.1.3: Multi-Drop Network Connections
A serially connected XPL/XP2 drive can be used as a multi-drop gateway for access to other
XPL/XP2 drives linked in a series of CAN bus connections. Set the CAN node address of the serially
connected drive (gateway) to zero (0). Assign each additional drive in the chain a unique CAN node
address value between 1 and 127. If the XP2 is used as the master, axis B is sequentially addressed
automatically. Also, when using XP2 as a master, axis A will not be available for CAN controls. Use
120 Ohms termination on the first and last drive.
PC, PLC, or HMI
for ASCII Control
Serial
COM port
for
RS-232
9pin D-sub
RJ11
Copley Am plifier
w ith ASCII
RS-232
SER-CK "Serial Cable Kit"
ADDRESS MUST BE SET
TO ZERO BEFORE
POWER-UP OR RESET.
CAN
ADDR
0
PC, PLC, or HMI
for ASCII Control
Serial
COM port
for RS-232
9pin D-sub
RJ11
Copley Amplifier
with ASCII RS-232
SER-CK "Serial Cable Kit"
ADDRESSES MUST BE
SET BEFORE POWER-UP
OR RESET.
CAN
ADDR
0
CAN Port
120 Ohm
Terminator
CAN
ADDR
CAN Port
CAN
ADDR
CAN Port
120 Ohm
Terminator
RJ45
CAN Network Cable UTP CAT.5E Gigabit Ethernet
CAN
ADDR
1
CAN Port
RJ45
RJ45
RJ45
RJ45
RJ45
2
TERMINATION MUST BE
USED ON FIRST AND LAST
NODE
Содержание XEL-230-18
Страница 1: ...123123 P N 16 01344 Revision 06 August 30 2019 Xenus Plus User Guide...
Страница 2: ...Xenus Plus User Guide 16 01344 Rev 06 This page for notes...
Страница 9: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 9 This page for notes...
Страница 18: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 18...
Страница 82: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 82 3 25 3 XE2 XP2 XM2 non N models 800 1819 Dimensions...
Страница 116: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 116 Optically Isolated Programmable Outputs Wiring Diagram...
Страница 120: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 120 Analog Input Wiring Diagram Multi Mode Port Interface Diagram...