Xenus Plus User Guide
16-01344 Rev 06
Copley Controls
142
At about 1.6 seconds, the I
2
T Accumulator Variable reaches a value equal to the I
2
T setpoint. At this
time, the drive limits the output current to the continuous current limit even though the commanded
current remains at 12 A. The I
2
T Accumulator Variable value remains constant during the next 2
seconds since the difference between the actual output current and the continuous current limit is
zero.
At approximately 3.5 seconds, the commanded current falls below the continuous current limit and
once again the output current follows the commanded current. Because the actual current is less
than the continuous current, the I
2
T Accumulator Variable value begins to fall incrementally.
The I
2
T Accumulator Variable value continues to fall until at approximately 5.0 seconds when the
commanded current goes above the continuous current limit again. The actual output current follows
the current command until the I
2
T Accumulator Variable value reaches the I
2
T setpoint and current
limiting is invoked.
Содержание XEL-230-18
Страница 1: ...123123 P N 16 01344 Revision 06 August 30 2019 Xenus Plus User Guide...
Страница 2: ...Xenus Plus User Guide 16 01344 Rev 06 This page for notes...
Страница 9: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 9 This page for notes...
Страница 18: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 18...
Страница 82: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 82 3 25 3 XE2 XP2 XM2 non N models 800 1819 Dimensions...
Страница 116: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 116 Optically Isolated Programmable Outputs Wiring Diagram...
Страница 120: ...Xenus Plus User Guide 16 01344 Rev 06 Copley Controls 120 Analog Input Wiring Diagram Multi Mode Port Interface Diagram...