Why can’t the STO function be deactivated?
•
The voltage between STO-IN1(+) and STO-IN1(-) is < 2.0 Vdc OR the voltage
between STO-IN2(+) and STO-IN2(-) is < 2.0 Vdc. Both of these voltages
must be ≥ 3.3 Vdc to deactivate the STO function
Why can’t the STO function be activated?
•
The voltage between STO-IN1(+) and STO-IN1(-) is > 3.3 Vdc AND the voltage
between STO-IN2(+) and STO-IN2(-) is > 3.3 Vdc. One or both of these voltages
must be < 2.0 Vdc to activate the STO function
The drive is hardware-
enabled but the motors don’t move.
•
The STO function may be active. Check object 0x219D to see if either bit 0 OR bit 1
is set (1). If either of bits 0 or 1 are set, or if both are set, then the
STO function will be activated.