Condensing Unit Controller EC2-5X1 

4 Parameters 

4.1 

Select parameter configuration 

The configuration parameters can be protected by a numerical password. A value of “0” 
disables this protection (default password: 12). To select the parameter configuration: 
 

 

Press the 

PRG

 button for more than 5 seconds  

 
In case of password value equal to “0”: 

 

The first modifiable parameter code is displayed (/1). 

 

To modify parameters see “Parameter modification” below. 

 
In case of password value not equal to “0”:  

 

A flashing 0 is displayed 

 

Press   or   until the password value is displayed. 

 

Press 

SEL

 to confirm password 

 

The first modifiable parameter code is displayed (/1). 

 

To modify parameters see Parameters modification below. 

 

4.2 Parameter 

Modification 

 

Press    or   to show the code of the parameter that has to be changed; 

 

Press 

SEL

 to display the selected parameter value;  

 

Press   or   to increase or decrease the value; 

 

Press 

SEL

 to temporally confirm the new value and display its code 

 
Repeat the procedure from the beginning "

press   or   to show..

." to modify another 

parameter, etc. 
 
To exit modifying the parameters with the new values: 

 

Press 

PRG

 to confirm the new values and exit the parameter modification 

procedure. 

 
To exit without modifying any parameter: 

 

Do not press any button for at least 60 seconds (TIME OUT). 

 

4.3 Special 

Functions 

 

Press   and   together for more than 5 seconds: a flashing “0” is displayed. 

 

 

Press   or   until the password is displayed (default = 12). If password was 
changed, select the new password. 

 

Then press 

SEL

 to confirm password 

 

A “0“ is displayed and the special function mode is activated. 

 

Press   or   to select function (see list below) 

 

Press 

SEL

 to activate the function and don’t leave the special function mode. 

 

Press 

PRG

 to activate the function and leave the special function mode. 

Most of the special functions work in a toggle mode, the first call activates the 
function and the second call deactivates the function. The indication of the 
function can only be displayed when the special function mode will be left. 
0:  

display test function 

3:  

resets all parameters to the default factory settings 

1 & 2:  not active for EC2-511 and EC2-551 

Part no: 3125495 

C6.1.3/0505-0705/E 

Содержание EazyCool EC2-5X1

Страница 1: ...Copeland EazyCoolTM outdoor condensing units Application Guidelines Controller EC2 5X1...

Страница 2: ...GURATION 8 4 2 PARAMETER MODIFICATION 8 4 3 SPECIAL FUNCTIONS 8 5 Indications on the Display 9 5 1 CONTROLLER 1 9 5 2 CONTROLLER 2 9 5 3 OTHER DISPLAY INDICATIONS 9 6 List of Parameters 9 6 1 CONTROLL...

Страница 3: ...ith a danger of explosion CAUTION This Icon indicates instructions to avoid property damage without or with low personnel injuries IMPORTANT This icon indicates instructions to avoid malfunction of th...

Страница 4: ...driver is installed available as a factory fitted option 2 1 EC2 5X1 Nomenclature Max 2 compressor with on off modulation Max 2 condenser fans with on off modulation Max 2 compressors with on off modu...

Страница 5: ...roller EC2 511 Controller For the measurement of the suction pressure and the condensing pressure two Alco Controls PT4 pressure sensors with 4 20 mA interfaces are connected to the condensing unit co...

Страница 6: ...are two controllers present in the EC2 551 controller one for controlling the compressor capacity and one for controlling the condenser pressure The control target of the compressor controller is to...

Страница 7: ...on pressure the condensing pressure and the saturation temperature from condensing pressure To scroll through all possible displayable data press the SEL button The display will show for one second th...

Страница 8: ...om the beginning press or to show to modify another parameter etc To exit modifying the parameters with the new values Press PRG to confirm the new values and exit the parameter modification procedure...

Страница 9: ...ntroller 2 parameter 5 3 Other display indications Pressure Pressure value in bar g Alarm Alarm condition IR IR communication enabled Service Transmission of Neuron ID indicator NOTE Concerning the in...

Страница 10: ...e around 2 bar in medium temperature and should be reset to around 0 4 bar for low temperature Dead band should be proportional to the pressure set point i e P0 0 4 P1 0 2 or P0 2 P1 1 3 This is a thr...

Страница 11: ...Hr 0 0 99 10k Hr 0 EC2 511 EC2 551 EC2 511 EC2 551 1 Value shown in display is 10 times lower 2 These values have a resolution of 10 000 hours on the local display Example value 1 means 10 000 hours...

Страница 12: ...act as modulating PWM control for Copeland Digital Scroll compressor only not in use for EC2 511 c5 Compressor switch logic 0 FILO logic FILO First In Last Out Capacity demand adds first compressor ou...

Страница 13: ...0 r3 Refrigerant type 0 5 4 0 5 4 EC2 511 EC2 551 r0 r1 parameters setting value depends of the refrigerant choice r3 r3 is set as default for R404A r3 Refrigerant 0 no temperature conversion 1 R22 2...

Страница 14: ...Sequence Unload Sequence Modulation parameter PWM Cycle Modulation cycle F2 20 4 sec F3 100 16 sec 20 0 4 10 20 0 4 10 PWM Cycle in sec Load Sequence Unload Sequence 20 F6 The Pulse Width Modulated si...

Страница 15: ...re 9 9 50 0 bar g 9 9 EC2 511 EC2 551 P0 Set point for fan modulation P1 Dead band default setting point is 4 bar Parameter t Time Parameters Min Max Unit Def Min Max Unit Def t1 1 Time delay before a...

Страница 16: ...Min Max Unit Def Min Max Unit Def r0 Condensing pressure sensor min value 1 0 50 0 bar 0 0 1 0 50 0 bar 0 0 r1 Condensing pressure sensor max value 1 0 50 0 bar 30 0 1 0 50 0 bar 30 0 r2 Pressure off...

Страница 17: ...e load compressor 2 compressor 1 act as modulating PWM control for Copeland Digital Scroll compressor only NOTE c4 parameter should be either 0 or 1 6 3 2 EC2 551 for Copeland EazyCool condensing unit...

Страница 18: ...tual pressure value of the system Controller 1 suction pressure higher than the maximum limit A3 inactive by default Controller 2 condensing pressure higher than the maximum limit A3 Alarm during the...

Страница 19: ...c6 numbers of compressors Controller 2 runs with c6 numbers of fans cE Communication error Controller 1 Communication error if binding for paralleling is used A slave controller then goes to emergency...

Страница 20: ...e service button will be pressed or a 30 min delay timer will expire or a second wink request NEURON ID oF Offline The node is offline no application is running This is the result of a network managem...

Страница 21: ...o 2 Pressure sensor 2 x 4 20 mA 2 wires Outputs 2 x Relays SPDT Imax 8A res 2A V AC max 250V Compressor relays 1 to 2 1 x Triac for 24 V AC Solenoid 1 x 0 10V Analog output Environmental pollution non...

Страница 22: ...3 Warszawa Tel 49 0 6109 6059 0 Tel 48 225 458 9205 Fax 49 0 6109 6059 40 Fax 48 225 458 9255 France Greece Maghreb Russia CIS 8 Allee Du Moulin Berger Letnikovskaya 10 building 2 5th floor F 69130 Ec...

Отзывы: