TROUBLESHOOTING STEPS

WHAT TO DO IF YOU HAVE A FAULT

MK4 CONTROL PANEL

 

 

RESET PROCESS (IF IN DOUBT, ASK)

1. Ensure the descent path of the curtain is clear i.e. there 
are no obstructions. The curtain will fully deploy during 
this process.
2. Remove the incoming ‘ALARM’ cable and the curtain 
should begin to deploy*. Wait for the curtain to have 
deployed to its fire operational position.
3. Remove the IEC power lead on top left hand side of 
control panel. This looks like a ‘kettle lead’.
4. Locate the ‘battery fuse’ on the underside of the bottom right hand side of the control panel. This is 
located in the centre of 3 circular, black fuses.
5. The fuse can be removed by applying pressure and twisting anti-clockwise. The fuse will then drop 
down slightly.
6. Wait 10 seconds and confirm that the MK4 remote display screen has lost power and has lost its 
display.
7. Re-instate the incoming power by re-connecting the IEC power lead (‘kettle lead’).
8. Re-connect the battery fuse by applying pressure and twisting clockwise. Confirm the battery fuse 
remains in position and does not drop down.
9. The MK4 will initialise and after 10 seconds should display ‘in MANUAL mode, AUTO press OK’.

VARIOSPEED

®

6 CONTROL PANEL  

(GREY BOX PANEL)

RESET PROCESS (IF IN DOUBT, ASK)

If the curtain has test / auto key on the front:
1. Ensure the descent path of the curtain is clear. i.e. there 
are no obstructions. The curtain will fully deploy during this 
process.
2. Turn the key to the ‘test’ position and the curtain should 
begin to deploy. Wait for the curtain to have deployed to its 
fire operational position.
3. Turn the key to the ‘Auto’ position.
4. The red ‘Alarm Off’ LED should start flashing/blinking.
5. Firmly press the ‘Reset’ button. 
Note: The curtain should begin to retract at this stage.

WWW.COOPERSFIRE.COM/SERVICE