INSTALLATION INSTRUCTIONS 

SPRM REMOTE MICROPHONE FOR USE WITH SP40S 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 

MODEL NUMBER: 

              SPRM

 

        108996 

       SPRM-B   109932 

 

GENERAL: 

The Remote Microphone is UL Listed under Standard 864, Control Units for Fire-Protective Signaling Systems. 

They are Listed for 

indoor use only

.  The Remote Microphone is designed to be used with Wheelock’s 

SP40S

 

SAFEPATH4

 Panel.  It provides a means 

for making emergency voice announcements from an auxiliary location.   Only 1 Remote Microphone can be connected to the 

SP40S

 

Panel.  The hand held push-to-talk microphone is supervised to ensure proper connection.  It is not repairable.  If it is detached from 
the unit, the unit must be returned for repair. 

 
 

NOTE

:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.  All warnings are printed in bold capital letters. 

 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.  FAILURE TO COMPLY 

WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER 
APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH 
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

SPECIFICATIONS: 

Power Input Voltage:         24VDC 
Audio Output Level:     1.05V RMS 
Output Impedance:        600 Ohms  
Min. Ground Fault:      20k Ohms 
Input 

Current:     Standby: 

23mA 

                    Alarm: 30mA 

 

WIRING DIAGRAM: 

 

Figure 1 shows the proper wiring connections for connecting the 

SPRM

 to the 

SP40S

 

REM

O

TE

 M

ICR
O

PHO
N

E

SP40S  PANEL

24V OUT

AUX IN

CC/NAC

+

-

+

-

TB6

24VDC

RM AUDIO

STATUS (CC)

-

+

-

+

6

5

4

3

2

1

+

-

+

-

*

*

 

 

Figure 1: 

*  This  wiring is power limited. 

NOTE

:  All wiring is supervised unless otherwise noted. 

WIRING SPECIFICATIONS: 

 

Cable Size: 

14-18 American Wire Gauge (AWG)  Shielded.  The shield must be connected only at the 

SP40S

 Panel. 

Maximum Length: 

2000 Feet 

Maximum Capacitance:  0.1uF/Total Run (50pF/foot for 1000 FT.) 
 