273 Branchport Avenue
Long Branch, NJ 07740
(800)
631-2148
Thank you for using our products.
www.cooperwheelock.com
INSTALLATION INSTRUCTIONS
SPRM REMOTE MICROPHONE FOR USE WITH SP40S
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
MODEL NUMBER:
SPRM
108996
SPRM-B 109932
GENERAL:
The Remote Microphone is UL Listed under Standard 864, Control Units for Fire-Protective Signaling Systems.
They are Listed for
indoor use only
. The Remote Microphone is designed to be used with Wheelock’s
SP40S
SAFEPATH4
Panel. It provides a means
for making emergency voice announcements from an auxiliary location. Only 1 Remote Microphone can be connected to the
SP40S
Panel. The hand held push-to-talk microphone is supervised to ensure proper connection. It is not repairable. If it is detached from
the unit, the unit must be returned for repair.
NOTE
:
All
CAUTIONS
and
WARNINGS
are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY
WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER
APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Power Input Voltage: 24VDC
Audio Output Level: 1.05V RMS
Output Impedance: 600 Ohms
Min. Ground Fault: 20k Ohms
Input
Current: Standby:
23mA
Alarm: 30mA
WIRING DIAGRAM:
Figure 1 shows the proper wiring connections for connecting the
SPRM
to the
SP40S
.
REM
O
TE
M
ICR
O
PHO
N
E
SP40S PANEL
24V OUT
AUX IN
CC/NAC
+
-
+
-
TB6
24VDC
RM AUDIO
STATUS (CC)
-
+
-
+
6
5
4
3
2
1
+
-
+
-
*
*
Figure 1:
* This wiring is power limited.
NOTE
: All wiring is supervised unless otherwise noted.
WIRING SPECIFICATIONS:
Cable Size:
14-18 American Wire Gauge (AWG) Shielded. The shield must be connected only at the
SP40S
Panel.
Maximum Length:
2000 Feet
Maximum Capacitance: 0.1uF/Total Run (50pF/foot for 1000 FT.)
Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
P84207 Rev. E
Sheet 1 of 4