INSTALLATION INSTRUCTIONS

 

www.cooperwheelock.com                         

SERIES NS-24MCC/MCCH MULTI-CANDELA HORN/STROBE 

(CEILING MOUNT VERSION)

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

GENERAL: 

Cooper Wheelock’s Series NS Multi-Candela ceiling mount Horn/Strobe (NS) requires only 2-wires for operation of the horn and strobe circuits and provides either 
four or two  selectable candela settings (15, 30, 75, 95 or 115, 117).  The NS is the ideal choice for applications where the audible silence feature is required.  The NS is 
UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired and UL Standard 464 for Audible Signal Appliances for 

indoor use only

.  It is molded 

with a mounting plate for use with a 4” backbox or 100mm European backbox (See Figure A and mounting procedures). This strobe model is Listed for 

ceiling 

mounting only

.  The NS uses a xenon flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective 

visible signaling. 

 

The horn portion of the NS can be field set to provide either Continuous Horn or Code 3 Horn and can be field set for High (HI) or Low (LO) dBA.   

NOTE:

  The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is specified by ANSI and 

NFPA 72 for standard emergency evacuation signaling.  

The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose. 

 

The NS Horn/Strobe can be used with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock power supplies to provide synchronized strobe and synchronized 
Code 3 signal. 

 

The NS Horn/Strobe is designed for use with either filtered DC (VDC) or unfiltered full-wave-rectified (VRMS) input voltage.  All inputs are polarized for 
compatibility with standard reverse polarity supervision of circuit wiring by a fire alarm control panel (FACP). 

 

 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS 
INJURY OR DEATH TO YOU AND/OR OTHERS.   

 

SPECIFICATIONS: 

 

Table 1:  UL Listed Models and Ratings

 

Model Regulated 

Voltage 

(VDC/VRMS) 

Voltage Range Limit  

Per UL 464 and UL 1971 

(VDC/VRMS) 

Strobe 

Candela 

(cd) 

NS-24MCC 24 

16.0-33.0  15/30/75/95 

NS-24MCCH 24 

16.0-33.0 

115/177 

 
 
 
 

Table 2:  dBA Sound Output for 24VDC Per UL 

Description 

Volume 

Reverberant dBA Per UL 464 

  

16.0VDC 

24.0VDC 

33.0VDC 

 Low 

78 

81 

84 

Continuous Horn 

High 

84 

88 

90 

 Low 

73 

77 

79 

Code 3 Horn 

High 

80 

83 

85 

NOTES:   

1.  The strobe will produce 1 flash per second over the "Regulated Voltage" range.   
2.  This horn/strobe model meets the required light distribution patterns defined in UL 1971. 
3.  All models are UL Listed for indoor ceiling use with a temperature range of +32

°

F to +120

°

F (0

°

C to +49

°

C) and maximum humidity of 93% 

±

 2% RH.  The 

effect of shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and not subjected to 
misuse or abuse.   

WARNING:  CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT. 

 

Table 3:  UL Current Ratings (AMPS) 

Maximum RMS Current with Hi dBA Setting 

Regulated Voltage 

15cd 

30cd 75cd 95cd 115cd 177cd 

DC 

16.0-33.0VDC  0.082 0.124 0.209 0.275  0.350  0.477 

FWR 

16.0-33.0VRMS 0.141 0.204 0.312 0.411  0.491  0.681 

Maximum RMS Current with Low dBA Setting 

Regulated Voltage 

15cd 

30cd 75cd 95cd 115cd 177cd 

DC 

16.0-33.0VDC  0.071 0.114 0.201 0.261  0.306  0.429 

FWR 

16.0-33.0VRMS 0.124 0.184 0.301 0.397  0.469  0.659 

 
 

When calculating the total current:  Use Table 3 to determine the highest value of “RMS Current” for an individual NS then multiply the value by the total number of 
NS Appliances.  Be sure to add the currents for any other appliances powered by the same source and to include any required safety factors. 

NOTE:  

The maximum number of strobes on a single notification appliance circuit shall not exceed 50. 

CAUTION:  

These notification appliances are UL Listed as “Regulated”.  They are intended to be used with FACPs whose notification circuits are UL Listed as 

“Regulated.”  These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the 
installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual. 

 