605
EMERGENCY LIGHTS
Architectural
COOPER LIGHTING - SURE-LITES
®
COOPER LIGHTING
ML
SERIES
METROLITE
M E T R O L I T E
E M E R G E N C Y L I G H T
D I M E N S I O N S
D E S C R I P T I O N
The Metrolite ML Series is the right choice for installations where aesthetics are a priority. With its
white finish and sculptured compact design the product blends in with the surroundings. Matching
remotes are available to insure a consistent appearance. The pleasing look is accompanied by a feature
rich design that provides fully adjustable heads with high efficiency halogen lamps making it easy to
direct ample light to the required areas. Each unit employs a quick mount universal back with hinged
access for hassle free installation.
21.6"
[549mm]
5.30"
[135mm]
1.90"
[48mm]
4.80"
[1221mm]
4.40"
[112mm]
11"
[280mm]
4.30"
[109mm]
5.30"
[135mm]
Rated Wattage
to 87 1/2 % of Rated D.C. Voltage
Lamp Information
Model
DC Voltage
1 1/2 Hours
Remote Wattage Available
Type
Wattage
Number
ML1
6
25
0
Bi-Pin Halogen
12W ea
029-66
ML2
6
50
26
Bi-Pin Halogen
12W ea
029-66
ML3
12
50
26
Bi-Pin Halogen
12W ea
029-45
ML4NC
6
14
0
Bi-Pin Halogen
6W ea
029-12
ML5NC
12
28
0
Bi-Pin Halogen
12W ea
029-45
E N E R G Y D AT A
Input Current (Max.)
ML1, ML2, ML3
120V = .3A
277V = .1A
ML4NC, ML5NC
120V = .085A
277V = .035A
O R D E R I N G I N F O R M AT I O N
E L E C T R I C A L R AT I N G S
Model Number
ML1
ML2
ML3
ML4NC
(1)
ML5NC
(1)
Options (add as suffix)
V
= Voltmeter
TDM
= Time Delay Monitor
Alternate Lamps
(2)
Accessories
(Order separately)
VS1
= Polycarbonate Vandal Shield
WG12
= Wire Guard
S A M P L E N U M B E R : M L 1
• Dual-voltage input
120/277VAC, 60Hz
• Injection-Molded, High-
Impact, Thermoplastic
Housing, Rated UL 94-5VA,
Designer-White Textured
Finish, Integral Mounting
Plate
• Glare Free Lens, Fully
Adjustable, Halogen Lamps
• Sealed Lead Calcium or
Nickel Cadmium Battery
Maintenance Free, Long
Life, Full Recharge time,
24 Hours (max.)
• Line-Latching,
Low-Voltage Disconnect,
Test Switch, AC Power
Indicator, Brownout Circuit
• Red LED High Charge
Indicator, Amber LED AC
Power Indicator
• UL 924, Life Safety NFPA
101, NEC/OSHA, Most
State and Local Codes
(1)
NC = Nickel Cadmium Battery.
(2)
Consult your Cooper Lighting Representative.