4
2
INSTALLATION
The DLC-PDC controller can be mounted anywhere that 15VDC can be provided, and with a wiring
distance within 500’ of the DLC-PD sensor. The sensor should be mounted per its Installation and
Maintenance Manual.
2.1
Power Connections
The DLC-PDC 15VDC power should be connected to Terminal 5 at the bottom of the controller
board; DC Common should be connected to Terminal 4 (see Figure 1).
2.2
Load Connections
The DLC-PDC Form C output has Common connected to Terminal 7 (LOAD RATING 3A MAX), the
Normally Open contact is connected to Terminal 6, and the Normally Closed contact is connected to
Terminal 8 (see Figure 1).
2.3
DLC-PD Sensor Connections
The DLC-PD sensor has three (3) wires. The Yellow wire should be connected to Terminal 1 at the
bottom of the controller board. The Black wire should be connected to Terminal 2 and the Red wire
should be connected to Terminal 3 (see Figure 1).
Figure 1: DLC-PDC with DLC-PD Sensor