IF 1604 • 03/10
Copyright © 2010, Cooper Industries, Inc.
Page 1
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
CHAMP
®
IEC HID Floodlight
NFMV Floodlight 150 - 400W
Installation & Maintenance Information
IF1604
CONTENTS
1.
Safety Instructions
2.
Conformity with Standards
3.
Technical Data
4.
Field of Application
5.
Application/Property
6.
Installation
7.
Maintenance/Servicing
8.
Repairs/Overhaul/Modification
9. Disposal/Recycling
1. SAFETY INSTRUCTIONS
Installation is to be performed by skilled electricians and instructed personnel in
accordance with national legislation, including the relevant standards and, where
applicable, in accordance with IEC 60079-17 on electrical apparatus for explosive
atmospheres. The national safety rules and regulations for prevention of accidents
and the following safety instructions, which are marked with an ( ) in these
operating instructions, must be observed.
- The floodlight must not be operated in Zone 0, 1, or 20 hazardous areas.
- The requirements of EN 61241-0 and -1 regarding excessive dust deposits and
temperature must be considered by the user.
- The technical data indicated on the floodlight is to be observed.
- Changes of the design and modifications to the floodlight are not permitted.
- The floodlight shall be operated as intended and only in undamaged and perfect
condition.
- Only genuine Cooper Crouse-Hinds (CC-H) spare parts may be used for
replacement.
- Avoid short time switch on / switch off mode.
- Repairs that affect the explosion protection (see national standard) may only be
carried out by Cooper Crouse-Hinds or a qualified electrician and will
subsequently have to be checked by an “expert.”
- Do not keep these operating instructions inside the light fitting during operation.
2. CONFORMITY WITH STANDARDS
The floodlight conforms to the standards specified in the EC-Declaration of
Conformity. It has been designed, manufactured, and tested according to the DIN
EN ISO 9001. 94/9 EC: Equipment and protective systems intended for use in
potentially explosive atmospheres.
The floodlight fulfills further requirements such as those of the EC directive on
electromagnetic compatibility (2004/108/EG).
The floodlights are intended for use in potentially explosive atmospheres in Zones
2, 21, and 22 in accordance with IEC 60079-15.
3. TECHNICAL DATA:
Category of application:
DEMKO 10 ATEX0907694:
CE 0359
II 3 G Ex nR II
II 2 D Ex tD A21 IP66
IECEx UL 09.0025:
Ex nR II
Ex tD A21 IP66
Type of lamps:
High Pressure Sodium:
150 W HSE / HIT
250 W HSE / HIT
400 W HSE / HIT
Metal Halide:
250 W HIE / HIT
400 W HIE / HIT
Electrical Data:
Rated Voltage: 220V, 230V, 240 VAC
Rated Frequency: 50 Hz, 60 Hz
Rated Lamp Power: 150W, 250W, 400W
Degree of protection to EN/IEC 60529: IP 66
Insulation class acc. to EN 60598 / IEC 598I
Permissible Ambient Temperature: - 25°C...+40°C/+55°C
Perm. Storage Temperature in Original Packing: -40 ºC ... +60 ºC
Supply terminals: 6,0 mm² single or multi-wired
Cable entries metal thread:
M20 x 1, 5,
M25 x 1, 5,
3
⁄
4
’’ NPT
Dimensions: see dimensional drawings.
4. FIELD OF APPLICATION
The luminaire is intended for use in potentially explosive atmospheres Zone 2
according to IEC/EN 60079-10-1 and Zone 21 and Zone 22 in accordance with
IEC/EN 60079-10-2.
The enclosure materials used, including any external metal parts, are high quality
materials that ensure corrosion resistance and resistance to chemical substances
according to the requirements for use in a “normal“ industrial atmosphere.
-Copper-free aluminum.
-Stainless steel.
-Epoxy powder finish.
In case of use in an extremely aggressive atmosphere, please refer to
manufacturer.