Sensitivity Adjustments
Ultrasonic Sensitivity
(Green LED) – Using a small flathead screw driver turn
the green potentiometer so that the arrow points UP.
1. Stand in different areas of the room and wave your hands.
2. If the Green LED does not turn ON, increase the US sensitivity by turning
the green potentiometer clockwise in small increments.Repeat Step 1.
3. Stand still three to four feet away from sensor for five seconds. LED
should not turn ON.
4. If Green LED turns ON without motion or is constantly ON decrease the
US sensitivity by turning green potentiometer counter-clockwise in small
decrements. Repeat Step 3.
Note:
Do Not adjust sensitivity higher than necessary.
PIR Sensitivity
1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
3. Stand still three to four feet away from sensor for five seconds. LED should not turn ON.
4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50 % by moving DIP switch 5 up.
Field-of-view outside the space
1. Adjust PIR sensitivity to 50 % by moving
DIP switch 5 up.
2. Use non-reflective tape strips to cover the portions
of the sensor lens that view outside the space.
3. Adjust Ultrasonic sensitivity.
Daylight Adjustments
The Daylighting feature prevents the lights from turning ON when the room is adequately illuminated by natural light. If
there is enough light in the room, regardless of occupancy, the sensor will hold the lights OFF. If there is not enough light
in the room, the sensor will allow the lights to turn ON when occupied. The Daylighting feature allows the selection of
which relay to control via daylighting (dual load models only). The sensor will not allow the Daylighting feature to turn the
load OFF until the space is vacant if the light level rises above the setpoint and the time delay expires. While in Manual
Activation Mode, if someone attempts to turn the load ON and there is sufficient daylight available the Daylighting
feature will hold the lights OFF.
1. Set the light level when the ambient light is at the level where no artificial light is needed. If this feature is not
needed, leave the light level at maximum (fully CW).
2. Set DIP switches 11 (Relay 1) and/or 12 (Relay 2) for daylight control.
3. With the load(s) ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP switch 12 out of its current
position, wait 3 seconds and then back in to its original position.
4. Set the light level to minimum (fully CCW).
5. Let the sensor time-out so lights are OFF. Enter the space and lights should remain OFF.
6. Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small
increments. (Pause 5 seconds between each adjustment)
7. Lights will not turn ON upon occupancy activation, when the ambient light level exceeds the daylight
threshold setting.
Time Delay Adjustments
People who remain very still for long periods of time
may need a longer time delay than the default setting of 10
minutes. As long as the Self-adjusting feature is enabled, the
switch will respond to each pair of false-OFFs with no normal
OFF in between, by alternately making slight adjustments to
either time delay (by 2 minute increments) or sensitivity, so
there should be no need for manual adjustment. If manual
adjustment is desired, refer to Time Delay settings in DIP
switch legend.
Reset sensor time delay to factory settings by moving DIP switches 1 and 2 down. (If DIP switches 1 and 2 are
already down, toggle DIP switch 1 out of its current position, wait 3 seconds, and then back to its original position)
Override
The Override setting allows the sensor to operate as a service switch in the unlikely event of failure.
1. Move DIP switch 8 up.
2. The pushbutton can be used to manually turn lights ON or OFF.
Warranties and Limitation of Liability
DIP Switch Settings
Troubleshooting
Please refer to www.coopercontrol.com under the Legal section for our terms and conditions.
Checkout and Adjustment
LOAD 2
LOAD 1
BLACK
RED
BLUE
RED
NEUTRAL
GROUND
GREEN
120/277 VAC
BLACK
RED
BLUE
RED
GROUND
GREEN
TRAVELER
WIRES
THREE-WAY
THREE-W
THREE-W W
AY
AY IRING DIAGRAM:
LIGHTS WILL TURN OFF,
TURN OFF
TURN OFF WHEN UNIT THAT
THA
THA WAS
W
W
TURNED
ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
TIMES-OUT
TIMES-OUT
Wiring Diagram 3:
120/277 VAC dual level single circuit three-way wiring diagram
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit
per relay. Both circuits must be fed from the same phase.
Issue
Possible Causes
Suggestions
Lights
Will Not
Turn ON
automatically
Sensor is in Manual ON mode
Press pushbutton. If Auto Mode
is desired change Activation Mode to Auto
Sensor was turned OFF manually. If the
Sensor was turned OFF manually before
the time delay expired, lights will remain
OFF for the remainder of the time delay.
Check LEDs, if LEDs blink with motion. This is an
indication that the lights were turned OFF manually.
Press the pushbutton to turn the lights back ON
Daylighting Feature Enabled
If all lights are required to turn ON adjust
DIP Switches 11 and 12 and/or daylight potentiometer
Power interruption
Check incoming voltage and/or wiring
Lights
Will Not
Turn ON
manually
Daylighting Feature Enabled
If all lights are required adjust DIP Switches
11 and 12 and/or daylight potentiometer
Power interruption
Check incoming voltage and/or wiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override
Make sure sensor is not in Override mode
(DIP Switch 8 up)
Self-Adjust
If sensor is in Self-Adjust Mode, it may be
possible for the unit to have increased the time
delay to a 30 minute delay. If the lights do not
turn OFF after 30 minutes follow next step
30 Minute Delay
Maximum time delay is 30 Minutes. Check DIP
Switches to verify DIP Switch settings. If lights do
not turn OFF at the set Time Delay, check next step
Ultrasonic Sensitivity set High
Lower sensitivity by turning green
potentiometer CCW in small decrements
PIR activated by heat source
other than occupant
Move DIP Switch 5 up
Lights
Will Not
Turn OFF
manually
Call Technical Services
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
5 Minutes
Auto*
*Self-Adjusts to
10 min. user
mode
Time Delay
DIP Switch
Activation
PIR Sensitivity
Bathroom
Override
R
Bathroom
Bathroom
elay Swap
Daylighting
Relay 1
Relay 2
Relay 1
Relay 2
Maintain Lights On
Walk-Through Mode
Default =
30 Minutes
15 Minutes
1
2
DIP Switch Legend
12
Disable
Enable
11
Disable
Enable
9
Disable
Enable
6
Disable
Enable
4
Auto
Manual
3
Auto
Manual
5
Full
50%
8
Either
Both
7
Disable
Enable
10
Normal
Swap
1 2 3 4 5 6
7 8 9 10
11 12
Adjustments should be made with the HVAC system ON so that the installer will be able to detect the effect of
airflow on the operation of the ONW-D-1001-DMV. Use only insulated tools to make adjustments.
Immediately after applying power to the lighting circuit, wait approximately two minutes for the switch to power-up
and stabilize.
Self-Adjust
Sensor is shipped in Self-adjust mode. This applies to time delay,
US and PIR sensitivity. In preparation for the Installer Test, the time
delay is set to 15 seconds, after the sensor is installed, powered
ON and has stabilized, the unit will time-out 15 seconds after the
last motion detected. Coverage and sensitivity can be confirmed by
watching the Green (US) and Red (PIR) indicator LEDs on the front of
the sensor, while moving around the room.
1. Walk around the room and monitor LEDs.
2. Stand in different parts of the room and wave your hands
LEDs should only turn ON for one second with each motion.(If
LED does not turn ON, go to Installer Adjustment Section)
3. Stand still three to four feet away from sensor for five seconds.
LEDs should not turn ON. (If LED does turn ON, go to Installer
Adjustment Section)
4. Walk outside the room and wait 15 seconds for the lights to
turn OFF. (If lights do not turn OFF go to Installer Adjustments Section)
5. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
6. At this point you can exit the room and let the sensor time-out. When the sensor times-out and is OFF for five
minutes, the unit will go to a 10 minute Time Delay user mode setting.
Note:
To place into Test Mode, toggle DIP Switch 12 out of its current position, wait 3 seconds, and then back into its original position.
ON/OFF Buttons
PIR Lens
DIP Switches
Ultrasonic Detection
Sensor Level
Adjustment
Ultrasonic
Sensitivity
Adjustment
Red (PIR) & Gr
Detection LEDs
1 and 2
1
2
3 4 5 6 7 8 9 10 11 12
11 and 12
1 2 3 4 5 6
7 8 9 10
11 12
Installer Adjustments