Limited Warranty
DIP Switch Settings
Troubleshooting
All products manufactured by Cooper Controls and identified with the Greengate brand are warranted to be free from defects in
material and workmanship and shall conform to and perform in accordance with Seller’s written specifications for a period of: Five
(5) years from date of shipment for all occupancy sensors and Three (3) years from date of factory invoice for our hardware and
software on Lighting Control Panels. We warranty all our standard relays for a period of 10 years from date of factory invoice. We
guarantee the performance of our system to specifications or your money back. This warranty will be limited to the repair or
replacement, at Seller’s discretion, of any such goods found to be defective, upon their authorized return to Seller. This limited
warranty does not apply if the goods have been damaged by accident, abuse, misuse, modification or misapplication, by damage
during shipment or by improper service. There are no warranties, which extend beyond the hereinabove-limited warranty, INCLUD-
ING, BUT NOT LIMITED TO, THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS. No
employee, agent, dealer, or other person is authorized to give any warranties on behalf of the Seller or to assume for the Seller any
other liability in connection with any of its goods except in writing and signed by the Seller. The Seller makes no representation
that the goods comply with any present or future federal, state or local regulation or ordinance. Compliance is the Buyer’s respon-
sibility. The use of the Seller’s goods should be in accordance with the provision of the National Electrical Code, UL and/or other
industry or military standards that are pertinent to the particular end use. Installation or use not in accordance with these codes
and standards could be hazardous.
Cooper Controls
203 Cooper Circle, Peachtree City, GA 30269
800-553-3879
www.coopercontrol.com
P/N 910-0494
REV C
Checkout and Adjustment
120/277 VAC
BLACK
BLUE
NEUTRAL
GROUND
GREEN
LOAD 1
LOAD 2
LOAD 1
BLACK
BLUE
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTEDMOTION LAST TIMES-OUT.
GROUND
GREEN
120/277 VAC
BLACK
BLUE
GROUND
GREEN
TRAVELER
WIRES
Wiring Diagram 3:
120/277 VAC single level single circuit three-way wiring diagram
Wiring Diagram 2:
120/277 VAC single level switch dual level wiring using a toggle switch wiring diagram
there should be no need for manual adjustment. If manual adjustment is desired, refer to Time Delay settings in DIP
Switch legend.
Reset sensor Time Delay to factory settings by moving DIP Switches 1 and 2 down. (If DIP Switches 1 and 2 are
already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, and then back to its original position)
Override
The override setting allows the sensor to operate as a service switch in the unlikely event of failure.
1. Move DIP Switch 8 up.
2. The Pushbutton can be used to manually turn lights ON or OFF.
5 Minutes
Auto*
*Self-Adjusts to
10 min. user mode
Time Delay
DIP Switch
Activation
PIR Sensitivity
Override
Relay 1
Not Used
EcoMeter
Walk-Through Mode
Default =
30 Minutes
15 Minutes
1
2
DIP Switch Legend
6
q
p
Disable
Enable
4
3
q
q
q
q
q
p
p
p
p
p
Auto
Manual
5
q
p
Full
50%
8
q
p
p
q
7
Enable
Disable
Disable
Enable
1 2 3 4 5 6 7 8
Adjustments should be made with the HVAC system on so that the installer will be able to detect the effect of
airflow on the operation of the ONW-P-1001-MV. Use only insulated tools to make adjustments.
Immediately after applying power to the lighting circuit, wait approximately two minutes for the switch to power up
and stabilize.
Self-Adjust
Sensor is shipped in self-adjust mode. This applies to Time Delay and PIR sensitivity. In preparation for the
Installer Test, the Time Delay is set to 15 seconds, after the sensor is installed, powered ON and has stabilized, the
unit will Time-out 15 seconds after the last motion detected. Coverage and sensitivity can be confirmed by watch-
ing the Red (PIR) indicator LED on the front of the sensor, while moving around the room.
1. Walk around the room and monitor LEDs.
2. Stand in different parts of the room and wave your hands. LED should only turn ON for one second with
each motion. (If LED does not turn ON, go to Installer Adjustments – Sensitivity Adjustment Section)
3. Stand still three to four feet away from sensor for
five seconds. LED should not turn ON. (If LED turns
ON, go to Installer Adjustments – Sensitivity
Adjustments section)
4. Walk outside the room and wait 15 seconds for the
lights to turn OFF. (If lights do not turn OFF go to
Installer Adjustments Section)
5. Re-enter the room to activate sensor. (If lights do
not turn ON go to Troubleshooting Section)
6. At this point you can exit the room and let the sensor
Time-out. When the sensor times-out and is OFF
for five minutes, the unit will go to a 10 minute Time
Delay user mode setting.
Note:
To place i nto Test Mode, toggle DIP Switch 8 out of its current position, wait 3 seconds, and then back into its original position.
Installer Adjustments
PIR Sensitivity
1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
3. Stand still three to four feet away from sensor for five seconds. LED should not turn ON.
4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.
ON/OFF Disabled Feature
1. ON/OFF Button Disable Option – When selected this option disables the ON/OFF button and sensor becomes auto-
matic only control regardless of the setting for automatic or manual activation. This feature will not allow someone
to turn light(s) OFF via the Pushbutton while people are in common areas such as restroom, break room, and copy
room areas.
Field-of-view outside the space
1. Adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.
2. Use non-reflective tape strips to cover the portions of the sensor lens that
view outside the space.
Daylight Adjustments
The daylighting feature prevents the lights from turning ON when the room is
adequately illuminated by natural light. If there is enough light in the room regard-
less of occupancy, the sensor will hold the lights OFF. If there is not enough light in
the room, the sensor will allow the lights to turn ON when occupied. The sensor
will not allow the daylighting feature to turn the load OFF until the space is vacant or
the light level rises above the setpoint and the Time Delay expires. While in Manual
Activation Mode, if someone attempts to turn the load ON and there is sufficient daylight available the Daylighting feature will
hold the lights OFF.
• Set the light level when the ambient light is at the level where no artificial light is needed. If this feature is not
needed,leave the light level at maximum (fully CW).
1. With the load(s) ON, put the sensor into Test Mode. To place into Test Mode,
toggle DIP Switch 8 out of its current position, wait 3 seconds and then back in to its original position.
2. Set the Light level to minimum (fully CCW).
3. Let the sensor Time-out so lights are OFF. Enter the space and
lights should remain OFF.
4. Make sure not to block the sensor from the daylight source and
adjust the light level potentiometer CW in small increments. (Pause
5 seconds between each adjustment)
5. Once the lights are ON, the load connected to the sensor will not
turn ON if light levels are above the current illumination.
Time Delay Adjustments
People who remain very still for long periods of time may need a longer Time Delay than the default setting of 10 min-
utes. As long as the self-adjusting feature is enabled, the switch will respond to each pair of False-offs with no normal
OFF in between, by alternately making slight adjustments to either Time Delay (by 2 minute increments) or sensitivity, so
ON/OFF Button
PIR Lens
DIP Switches
Daylight
Sensor Level
Adjustment
Red (PIR)
Detection LEDs
1 2
3 4 5 6
7 8
DIP Switches
1 & 2
Issue
Possible Causes
Suggestions
Lights
Will Not
Turn ON
automatically
Sensor is in Manual ON mode
Press Pushbutton. If Auto Mode
is desired change Activation Mode to Auto.
Sensor was turned OFF manually. If the Sensor
was turned OFF manually before the Time Delay
expired, lights will remain OFF for the remainder
of the Time Delay.
Check EcoMeter LED. If LED is ON this is
an indication that the lights were turned OFF manually.
Press the Pushbutton to turn the lights back ON.
Daylight Feature Enabled
If all lights are required to turn ON
adjust daylight potentiometer.
Power interruption
Check incoming voltage and/or wiring.
Lights
Will Not
Turn ON
manually
Daylight Feature Enabled
If all lights are required to turn ON
adjust daylight potentiometer.
Power interruption
Check incoming voltage and/or wiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override
Make sure sensor is not in Override Mode (DIP Switch 8 up).
Self-Adjust
If sensor is in Self-Adjust Mode, it may be possible for the
unit to have increased the Time Delay to a 30 minute delay.
If the lights do not turn OFF after 30 minutes follow next step.
30 Minute Delay
Maximum Time Delay is 30 Minutes. Check DIP Switches
to verify DIP Switch settings. If lights do not turn OFF at the
set Time Delay, check next step.
PIR activated by heat source other than occupant
Move DIP Switch 5 up.
Lights
Will Not
Turn OFF
manually
Call Technical Services
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Printed in Malaysia
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only
one circuit per relay. Both circuits must be fed from the same phase.