Limited Warranty

DIP Switch Settings 

Troubleshooting

All products manufactured by Cooper Controls and identified with the Greengate brand are warranted to be free from defects in
material and workmanship and shall conform to and perform in accordance with Seller’s written specifications for a period of: Five
(5) years from date of shipment for all occupancy sensors and Three (3) years from date of factory invoice for our hardware and
software on Lighting Control Panels. We warranty all our standard relays for a period of 10 years from date of factory invoice.  We
guarantee  the  performance  of  our  system  to  specifications  or  your  money  back.  This  warranty  will  be  limited  to  the  repair  or
replacement, at Seller’s discretion, of any such goods found to be defective, upon their authorized return to Seller. This limited
warranty does not apply if the goods have been damaged by accident, abuse, misuse, modification or misapplication, by damage
during shipment or by improper service. There are no warranties, which extend beyond the hereinabove-limited warranty, INCLUD-
ING,  BUT  NOT  LIMITED  TO,  THE  IMPLIED  WARRANTY  OF  MERCHANTABILITY  AND  THE  IMPLIED  WARRANTY  OF  FITNESS.  No
employee, agent, dealer, or other person is authorized to give any warranties on behalf of the Seller or to assume for the Seller any
other liability in connection with any of its goods except in writing and signed by the Seller.  The Seller makes no representation
that the goods comply with any present or future federal, state or local regulation or ordinance.  Compliance is the Buyer’s respon-
sibility.  The use of the Seller’s goods should be in accordance with the provision of the National Electrical Code, UL and/or other
industry or military standards that are pertinent to the particular end use.  Installation or use not in accordance with these codes
and standards could be hazardous.

Cooper Controls
203 Cooper Circle, Peachtree City, GA 30269
800-553-3879
www.coopercontrol.com 

P/N 910-0494     
REV C

Checkout and Adjustment 

120/277 VAC

BLACK

BLUE

NEUTRAL

GROUND

GREEN

LOAD 1

LOAD 2

LOAD 1

BLACK

BLUE

NEUTRAL

THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTEDMOTION LAST TIMES-OUT.

GROUND

GREEN

120/277 VAC

BLACK

BLUE

GROUND

GREEN

TRAVELER 
WIRES

Wiring Diagram 3: 

120/277 VAC single level single circuit three-way wiring diagram

Wiring Diagram 2: 

120/277 VAC single level switch dual level wiring using a toggle switch wiring diagram

there should be no need for manual adjustment. If manual adjustment is desired, refer to Time Delay settings in DIP

Switch legend.

Reset sensor Time Delay to factory settings by moving DIP Switches 1 and 2 down.  (If DIP Switches 1 and 2 are

already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, and then back to its original position)  

Override

The override setting allows the sensor to operate as a service switch in the unlikely event of failure.

1. Move DIP Switch 8 up.

2. The Pushbutton can be used to manually turn lights ON or OFF. 

5 Minutes

Auto*

*Self-Adjusts to

10 min. user mode

Time Delay

DIP Switch

Activation

PIR Sensitivity

Override

Relay 1

Not Used

EcoMeter

Walk-Through Mode

Default = 

30 Minutes

15 Minutes

1

2

DIP Switch Legend

6

q
p

Disable

Enable

4

3

q

q

q

q
q

p

p

p

p

p

Auto

Manual

5

q
p

Full

50%

8

q
p

p

q

7

Enable

Disable

Disable

Enable

1 2 3 4 5 6 7 8

Adjustments  should  be  made  with  the  HVAC  system  on  so  that  the  installer  will  be  able  to  detect  the  effect  of 

airflow on the operation of the ONW-P-1001-MV.  Use only insulated tools to make adjustments.

Immediately after applying power to the lighting circuit, wait approximately two minutes for the switch to power up

and stabilize.

Self-Adjust 

 Sensor  is  shipped  in  self-adjust  mode.    This  applies  to  Time  Delay  and  PIR  sensitivity.    In  preparation  for  the

Installer Test, the Time Delay is set to 15 seconds, after the sensor is installed, powered ON and has stabilized, the
unit will Time-out 15 seconds after the last motion detected.   Coverage and sensitivity can be confirmed by watch-
ing the Red (PIR) indicator LED on the front of the sensor, while moving around the room.  

1. Walk around the room and monitor LEDs.  
2. Stand  in  different  parts  of  the  room  and  wave  your  hands.    LED  should  only  turn  ON for  one  second  with 

each motion.  (If LED does not turn ON, go to Installer Adjustments – Sensitivity Adjustment Section)

3. Stand  still  three  to  four  feet  away  from  sensor  for 

five seconds.  LED should not turn ON.  (If LED turns 
ON,  go  to  Installer  Adjustments  –  Sensitivity 
Adjustments section)

4. Walk outside the room and wait 15 seconds for the 

lights to turn OFF.  (If lights do not turn OFF go to 
Installer Adjustments Section)

5. Re-enter the room to activate sensor.  (If lights do 

not turn ON go to Troubleshooting Section)

6. At this point you can exit the room and let the sensor

Time-out.    When  the  sensor  times-out  and  is  OFF
for five minutes, the unit will go to a 10 minute Time
Delay user mode setting.

Note:

To place i  nto Test Mode, toggle DIP Switch 8 out of its current position, wait 3 seconds, and then back into its original position. 

 

Installer Adjustments

PIR Sensitivity

1. Stand in different areas of the room and wave your hands.

2. If the Red LED does not turn ON, check for any obstructions.

3. Stand still three to four feet away from sensor for five seconds.  LED should not turn ON.

4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.

ON/OFF Disabled Feature

1. ON/OFF Button Disable Option – When selected this option disables the ON/OFF button and sensor becomes auto-

matic only control regardless of the setting for automatic or manual activation.  This feature will not allow someone 

to turn light(s) OFF via the Pushbutton while people are in common areas such as restroom, break room, and copy 

room areas.

Field-of-view outside the space

1. Adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.

2. Use non-reflective tape strips to cover the portions of the sensor lens that 

view outside the space.

Daylight Adjustments

The daylighting feature prevents the lights from turning ON when the room is

adequately illuminated by natural light.  If there is enough light in the room regard-

less of occupancy, the sensor will hold the lights OFF.  If there is not enough light in

the room, the sensor will allow the lights to turn ON when occupied.  The sensor

will not allow the daylighting feature to turn the load OFF until the space is vacant or

the light level rises above the setpoint and the Time Delay expires.  While in Manual

Activation Mode, if someone attempts to turn the load ON and there is sufficient daylight available the Daylighting feature will

hold the lights OFF. 

•   Set the light level when the ambient light is at the level where no artificial light is needed.  If this feature is not 

needed,leave the light level at maximum (fully CW). 

1.  With the load(s) ON, put the sensor into Test Mode.  To place into Test Mode, 

toggle DIP Switch 8 out of its current position, wait 3 seconds and then back in to its original position.    

2. Set the Light level to minimum (fully CCW). 
3. Let the sensor Time-out so lights are OFF. Enter the space and 

lights should remain OFF. 

4. Make sure not to block the sensor from the daylight source and 

adjust the light level potentiometer CW in small increments. (Pause 
5 seconds between each adjustment) 

5. Once the lights are ON, the load connected to the sensor will not 

turn ON if light levels are above the current illumination. 

Time Delay Adjustments

People who remain very still for long periods of time may need a longer Time Delay than the default setting of 10 min-

utes.  As long as the self-adjusting feature is enabled, the switch will respond to each pair of False-offs with no normal

OFF in between, by alternately making slight adjustments to either Time Delay (by 2 minute increments) or sensitivity, so

ON/OFF Button

PIR Lens

DIP Switches

Daylight 

Sensor Level 

Adjustment

Red (PIR)

Detection LEDs

1 2

3 4 5 6

7 8

DIP Switches

1 & 2

Issue

Possible Causes

Suggestions

Lights 

Will Not

Turn ON 

automatically

Sensor is in Manual ON mode

Press Pushbutton.  If Auto Mode

is desired change Activation Mode to Auto.

Sensor was turned OFF manually.  If the Sensor

was turned OFF manually before the Time Delay
expired, lights will remain OFF for the remainder 

of the Time Delay.  

Check EcoMeter LED.  If LED is ON this is 

an indication that the lights were turned OFF manually.  

Press the Pushbutton to turn the lights back ON.

Daylight Feature Enabled

If all lights are required to turn ON

adjust daylight potentiometer.

Power interruption

Check incoming voltage and/or wiring.

Lights 

Will Not 

Turn ON 

manually

Daylight Feature Enabled

If all lights are required to turn ON

adjust daylight potentiometer.

Power interruption

Check incoming voltage and/or wiring.

If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879

Lights 

Will Not 

Turn OFF 

automatically

Override

Make sure sensor is not in Override Mode (DIP Switch 8 up).

Self-Adjust

If sensor is in Self-Adjust Mode, it may be possible for the

unit to have increased the Time Delay to a 30 minute delay.  

If the lights do not turn OFF after 30 minutes follow next step.

30 Minute Delay

Maximum Time Delay is 30 Minutes.  Check DIP Switches 

to verify DIP Switch settings.  If lights do not turn OFF at the

set Time Delay, check next step.

PIR activated by heat source other than occupant

Move DIP Switch 5 up.

Lights 

Will Not 

Turn OFF 
manually

Call Technical Services

If lights will still not turn OFF, call Technical Services at 1-800-553-3879

Printed in Malaysia

CAUTION:  If a room is wired for two circuits using two separate hot leads, it is very important to connect only
one circuit per relay.  Both circuits must be fed from the same phase.