background image

Circulating Air Source Heat Pump Water Heater

 

23 

strainer is blocked, whether the air discharged and whether the resistance for the pipeline system is too 
big. ΔT should be 3

5

.   

5

After test run is finished, clean the strainer on the pipeline before normal operation. After a 

period of time (eg: three months), remove and clean the strainer periodically 

eg: every month

  for 

ensuring normal operation of the unit.   

6

During test run period, if the interval of stop operation for compressor is less than 3mins, do not 

turn on the unit with hand. If the operation is no more than 6mins, do not stop operation with hand.   

Note: Because the unit adopts totally-enclosed scroll compressor, the phase sequence of power 

must be correct.     

6.3 Daily operation and maintenance   

1

At the time of ex-factory time, all the safety protection switches have been sent. Users can’t 

adjust or eliminated it by themselves.   

2

For the first operation of the unit or restart up the unit when the unit has been cut off power for 

a long time (24h above), connect the supply power of the unit in advance to preheat the unit for 8hours 
above for avoiding damage to the compressor.   

3

Do not pile up sundries on the unit and accessories. The surroundings of the unit should be 

kept dry, clean and well-ventilated. If there’s too much dust on the fins of the condenser, please eliminate 
them in time to prevent affecting performance of unit.   

4

Clean the strainer inside the water system periodically to prevent protection or damage to the 

unit due to blockage of the water system. Meanwhile, frequently check whether the water supplement 
device inside the water system is normal.   

5

If the ambient temperature in winter is below 0

, prohibit cutting off the power. When the unit 

won’t be used for a long time, you should not only discharge the water

 inside the water system, but also 

remove the choke plug of water tank to discharge the water inside the water tank for preventing damage 
to the parts inside the unit.   

6

Do not turn on or turn off the unit frequently. Do not close the regulator valve of water system 

with hand freely during operation.   

7

Please check the working status of all parts of the unit. Check whether there’s grease on the 

pipeline joints inside the unit and refrigerant-charging valve to make sure there’s refrigerant leakage. If 
there’s leakage, please contact local appointed maintenance center for maintenance.   

8

If there’s malfunction for the unit and the user can’t solve it, please contact local appointed 

maintenance center in time.   

7 Troubleshooting   

Caution:  If  there’s  malfu

nction  during  operation  process,  please  contact  local  deader  or 

appointed maintenance center.   

1

Below phenomenons are not belong to malfunction:   

1

During operation in winter, the surface temperature of the heat exchanger is lower than outdoor 

ambient temperature, and when the surface temperature is lower than 0

, there will be frost on the 

surface of heat exchanger, which will affect the heat-exchanging efficiency. Therefore, the control system 

Содержание CH-HP20CMFNM

Страница 1: ... HP40CMFNM Thank you for choosing Air Source Heat Pump Water Heater please read this owner s manual carefully before operation and retain it for future reference Circulating Air Source Heat Pump Water Heater Owner s Manual Библиотека СОК ...

Страница 2: ......

Страница 3: ...ck whether the power is consist with that required on the nameplate and then check the safety of the power 2 Before operation please check and confirm whether electric wires and water pipes are connected correctly for preventing water leakage electric shock fire hazard and other accidents 3 The power socket must be equipped with earthing wire for ensuring reliable grounding for unit and preventing...

Страница 4: ...nment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was purchased They can take this product for environmental safe recycling When there re any problems please contact dealer appointed maintenance center o...

Страница 5: ... Before installation 6 3 2 Position before installation 6 3 3 Movement and installation of the unit 6 3 4 Installation space 7 3 5 Installation of circulating water system 8 3 6 Install the water flow switch 9 3 7 Construction and installation for the heating water tank 10 3 8 System installation diagram and instruction 11 4 Electric installation 16 5 DIP switch setting on main board 20 6 Debuggin...

Страница 6: ...stem Backwater pipe Condenser Evaporator Fan Air source energy input Electric energy input Electronic expansion valve Strainer Compressor Water supply pipe Water tank Inlet pipe of cold water Bushing condenser Exit pipe of hot water Gas liquid separator 1 3 Product features High efficiency and energy saving Adopt heat pump technology which can transfer the consumed electricity into three times of ...

Страница 7: ...odel Hot water mode Heating capacity kW 20 22 29 77 40 19 Heating Power Input kW 8 52 8 87 13 27 Heating Current Input A 13 9 16 9 26 Nominal Water Output L h 602 775 1140 Rated Input kW 10 1 13 2 19 Rated current Input A 20 24 38 Set temperature defaulted at 50 30 60 adjustable water tank temperature Power 380 415V 3N 50Hz Refrigerant Name R410A R410A R410A Refrigerant charge volume kg 4 2 4 2 5 ...

Страница 8: ...se is tested in the semi silencing room The actual noise will be a little higher in the actual operation environment Circulating water flow means the rated flow during the heating operation When selecting the water pump model it shall refer to the flow after overcoming the water resistance that is the flow of corresponding delivery lift rather than the maximum flow labeled in the nameplate of wate...

Страница 9: ... temperature Circulating water flow 6 2m 3 h Outdoor ambient temperature wet dry bulb 20 15 7 8 7 6 20 15 30 22 35 24 46 28 Heating Capacity kW 50 12 51 14 00 15 04 26 99 34 89 38 16 38 38 43 27 40 12 70 14 62 18 70 27 73 36 08 41 68 40 41 44 32 30 12 81 15 46 20 76 29 77 39 15 44 85 43 48 47 07 Heating Power Input kW 50 9 39 9 49 9 62 11 06 11 12 10 91 11 06 11 41 40 7 85 8 00 8 35 9 29 9 46 9 38...

Страница 10: ...Circulating Air Source Heat Pump Water Heater 5 2 4 Schematic plan for the unit outline Unit mm CH HP40CMFNM Unit mm CH HP20CMFNM CH HP30CMFNM ...

Страница 11: ...or any other places where s convenient for installation and bear the weight of the unit 2 The unit should be installed the well ventilated place and avoid the air discharge and noise disturb other people Please pay attention to the wind direction and avoid the strong wind 3 When placing the unit on the roof please pay attention to the wind direction to prevent strong wind 4 There should be no stro...

Страница 12: ...n the ground or roof Please confirm that the unit is placed horizontally See below fig 5 In case that the water heater is not under the lightning protection of the building then lightning protection measures should be taken according to the existing local national standards 3 4 Installation space 1 Single unit installation space for CH HP20CMFNM CH HP30CMFNM CH HP40CMFNM Unit mm 2 Modular unit ins...

Страница 13: ...tally and reasonably Try to reduce elbows as much as possible for decreasing the resistance of water system 7 Water pipe must be thermal insulated to prevent heat loss The common thermal insulation materials are PEF glass cotton rubber insulation sponge etc 8 Thermometer and water pressure gauge should be installed at the water inlet pipe and water outlet pipe of unit for inspection during operati...

Страница 14: ...that are 45mm 65mm 75mm or 85mm s long and 16mm s wide The paddle can be trimmed conditionally during installation Please make sure the rear part forms an arc that matches the pipe and the bottom of the paddle should be 10 20 above the pipe central line thus avoiding collision between the paddle and the inner surface of pipes as well as other objects inside water flow switch other valve fluid dire...

Страница 15: ...igher than the circulating water outlet to prevent water lacking during operation 2 The overflow port should be 50mm maximum higher than the water level switch to prevent overflow of water tank The overflow port must be connected with connection pipe and then lead it to the flow drainage outlet 3 The hot water inlet and the user back water outlet should point at the water level switch to prevent i...

Страница 16: ...diagram for signal unit system Fig1 Timer water supply installation diagram for single unit 2 Installation diagram for modular system Fig2 Timer water supply installation diagram for modular series Fig3 Non timer water supply installation diagram for modular unit the height of heating water tank is same as that of hot water storage tank ...

Страница 17: ...e low water level the water discharge solenoid valve water discharge pump between heating water tank and thermal storage water tank will be started up and then fill the thermal storage water tank with water If the water level switch of the thermal storage water tank is at the high water level the water discharge solenoid valve between heating water tank and thermal storage water tank water dischar...

Страница 18: ... the water temperature is increased to a certain temperature above set temperature backwater pump or backwater solenoid valve will be stopped for ensuring the water temperature requirement If user has requirement for water supply pressure Users are suggested to adopt water pump electric contact type pressure switch When the water pressure is lower than set value the water pump will be started up w...

Страница 19: ...tion diagram for the single unit system 2 Installation diagram for the modular system Instalaltion principle instruction 1 In order to prevent water freezing in the water side heater exchanger and pipeline add ethanol and propyl alcohol in water However prohibit adding salt into water for preventing corrosion and damage to the unit The water side heat exchanger inside the unit can t comply with th...

Страница 20: ...circulating water pump will make the water inside the swimming pool pass through removable plate type heat exchanger for the second time heat exchanger When the water temperature in the swimming pool reaches the set temperature the unit will stop operation Because swimming pool system is the second time heat exchanging there s temperature difference of heat exchanging at unit side and swimming poo...

Страница 21: ...struction manual by professional person Caution If the wiring is changed due to improvement of product please refer to the wiring diagram on the unit Caution For the consideration of safety the leakage protection device at the power side The detailed position is as shown in below fig Project electric cabinet Leakage protection device Leakage protection device Leakage protection device Leakage prot...

Страница 22: ...Circulating Air Source Heat Pump Water Heater 17 ...

Страница 23: ... can let the temperature wire support 100N tension force 2 Slave module 3 Connection among modules CN15 CN25 CN15 CN25 CN25 CN15 Wired controller 1 unit 2 unit 3 unit CN2 CN1 inspection board 4 Wiring layout If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Disconnect the power supply before cleaning an...

Страница 24: ...n Stationary appliances not fitted with means for disconnection from the supply mains having a contact separation in all poles that provide full disconnection under overvoltage category III the instructions state that means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules Model Power type Min sectional area of power cord mm 2 Capacity of air switch A L...

Страница 25: ...g Water Remark 3 Refer to item 3 in 5 Safety Notices for Using Water 5 DIP switch setting on main board Note 1 This instruction is only applicable for the main board of water heater 2 Please ask professional person to operate the DIP 3 Cut off the power before operating the DIP There are two groups DIP for the main board of water heater The first SA3 4 bit DIP group is the address DIP for the unit...

Страница 26: ...s are 2 3 16 in turn Because all the units are the same you can appointed the most convenient unit in the product as the 1 unit and connect wires according to the wiring diagram of master unit in this instruction manual Address DIP of unit black part is the deflector rod DIP Position Address Instruction SA3 1 2 3 4 ON pull the deflector rod to the direction of ON the opposite direction is OFF ON O...

Страница 27: ... the control wiring are connected correctly and tightly whether the grounding is reliable and whether all wiring terminals are fixed tightly 6 2 Test run Note Test run must be conducted when all above checkup items are qualified and guided by professional persons 1 Energize the unit and then turn on the unit As for the unit adopting three phase power if the power cord is connected reversely the ph...

Страница 28: ...lean the strainer inside the water system periodically to prevent protection or damage to the unit due to blockage of the water system Meanwhile frequently check whether the water supplement device inside the water system is normal 5 If the ambient temperature in winter is below 0 prohibit cutting off the power When the unit won t be used for a long time you should not only discharge the water ins...

Страница 29: ...quence Check it and connect it tightly Check the malfunction causes and resolve it Set it again Replace compressor Big noise for fan The fixing bolt for the fan is loose Blades touch outer case or grille The fan can t operate placidly Tighten the fixing bolts of fan Check it and adjust it Replace the fan Big noise for the compressor There s liquid slugging when liquid refrigerant entering into com...

Страница 30: ...erature sensor Floor heating mode OFF Hot water mode Auto F9 Malfunction of water outlet temperature sensor Floor heating mode OFF Hot water mode Auto E1 High pressure protection OFF Auto E3 Low pressure protection OFF Auto E4 Discharge high temperature sensor protection OFF Auto E5 Overload protection for compressor OFF Auto E6 Communication malfunction OFF Auto E0 Overload protection of water pu...

Страница 31: ...wo times within 40mins the reset method should be switched to manual from auto type 4 If low overload protection for compressor or fan motor is detected for the three times within 30mins the reset method should be switched to manual from auto type If there s quality problem or the unit can t operate normally within the warranty period please contact local maintenance center for free repair User mu...

Страница 32: ......

Отзывы: