Heat Pump
Unitherm 3 R32
25
Notes
(a) No additional charge of the refrigerant is need when the pipe length is less than 10m, if the pipe length is
longer than 10m, additional charge of the refrigerant is needed according to the table.
(b) Example: If 10kW model is installed at a distance of 25m, (25-10)x16=240g refrigerant should be added
.
Rated capacity is based on standard pipe length and maximum allowable length is based on the product
reliability in the operation. Oil trap should be installed every 5-7 meters when the location of outdoor unit is
higher than indoor unit.
9. Remote Air Temperature Sensor
Front side Back side
Remote Air Temperature Sensor
Doors
NO
NO
NO
NO
1.5 Meters
YES
AP
RT6
CN1
15K
CN8
Remote Air Environment
Temp sensor
Electric box
PCB
2
Notes
(a) Distance between the indoor unit and the remote air temperature sensor should be less than 15m due to
length of the connection cable of remote air temperature sensor;
(b)
Height from floor is approximately 1.5m;
(c)
Remote air temperature sensor cannot be located where the area may be hidden when door is open;