Page | 29
Down Key
Each press of the
Down Arrow
key decrements or reduces the values or
settings on the
SV
display.
Up Key
Each press of the
Up Arrow
key increments or advances the values or
settings on the
SV
display.
5-5 Auto-Tuning PCA Series Chillers
The Auto-Tune function lets you fine-tune the control PID to process requirements. Activate
the Auto-Tune function whenever the process under control changes. Don't be alarmed by
control
response. It may take the process temperature above and below the set points as many as
three (3) times. It will then level off and control to the process set point.
Auto tuning can
take up to 45 minutes
, and is best done before any product is being run.
Important!
Factory default settings are: P = .3, I = 7, and D = 1
To auto-tune the controller:
Press and hold down the
AT AT
key for several seconds until the
AT
indicator flashes.
The
AT
LED flashes to indicate that the control is tuning itself.When the
AT
LED light stops
flashing, the controller is tuned and ready for operation.
Important!
Do not change any of the control settings without consulting
the Fleming Dynamics Service Department.
The Fleming Dynamics Pty Ltd warranty does not cover chiller failures
from tampering with controller settings
!
Содержание PCA050
Страница 11: ...Page 11...
Страница 12: ...Page 12...
Страница 13: ...Page 13 BSP BSP BSP inches BSP inches BSP...
Страница 20: ...Page 20...
Страница 21: ...Page 21...
Страница 22: ...Page 22...
Страница 23: ...Page 23...
Страница 25: ...Page 25...
Страница 32: ...Page 32...
Страница 34: ...Page 34...
Страница 35: ...Page 35...
Страница 36: ...Page 36 Notes...
Страница 37: ...Page 37...
Страница 38: ...Page 38...
Страница 39: ...Page 39...
Страница 40: ...Page 40 Notes...
Страница 41: ...Page 41 Notes...
Страница 42: ...Page 42 Notes...