
Page | 19
3-3 High Pressure Cutout
The high pressure cutout is an electro-mechanical safety feature that opens the control
circuit if the system condensing pressure exceeds a safe level. The chiller will
automatically restart when the pressure drops back to an acceptable level.
Model
Cuts out if condensing pressure exceeds:
PCA050
1.897 Bar
PCA100
1.897 Bar
PCA150
2.759 Bar
IMPORTANT!
Call Fleming Dynamics to arrange a service technician to analyse the problem if high
pressure recurs.
3-4 Low Pressure Cut-out
The low pressure cut-out is an electro-mechanical safety feature that prevents compressor
suction pressure from dropping below a pre-set point.
It is factory set to open the control circuit when pressure drops below a safe level. The chiller
will automatically restart when the suction pressure reaches an acceptable level.
Model
Cuts out if suction pressure falls below:
PCA050
1.03 Bar
PCA100
1.03 Bar
PCA150
2.41Bar
3-5 Remote Start/Stop Interlock
A contact is provided to allow interlocking of the PCA Series Chiller with process controls. To
use this feature, remove the jumper between Terminals X1 and 1 on Terminal Block 1.
Supply a switch or dry contact interlock connected in series between these two terminals.
See Figure 15 and Figure 16 on pages 34 and 35 for more information.
Содержание PCA050
Страница 11: ...Page 11...
Страница 12: ...Page 12...
Страница 13: ...Page 13 BSP BSP BSP inches BSP inches BSP...
Страница 20: ...Page 20...
Страница 21: ...Page 21...
Страница 22: ...Page 22...
Страница 23: ...Page 23...
Страница 25: ...Page 25...
Страница 32: ...Page 32...
Страница 34: ...Page 34...
Страница 35: ...Page 35...
Страница 36: ...Page 36 Notes...
Страница 37: ...Page 37...
Страница 38: ...Page 38...
Страница 39: ...Page 39...
Страница 40: ...Page 40 Notes...
Страница 41: ...Page 41 Notes...
Страница 42: ...Page 42 Notes...