Thank you for choosing Coolmay FX3GC series PLC. This manual mainly explains the features, general
specifications and wiring methods of FX3GC series. More detail programming information please refer to
"Coolmay CX3G&FX3GC PLC Programming Manual".
The FX3GC series is a compact PLC with the following features:
1. Highly integrated. Digital at most 16DI/16DO (digital type can be customized transistor, relay or mixed).
Analog at most 8AI 6AO, input can be customized temperature, current, voltage or mixed (support-5~5V/
-10V~10V), output can be customized current and voltage.
2. Comes with two PLC programming ports: MiniB USB port (faster download speed) and RS232 port.
3. Support multi-channel high-speed counting and high-speed pulse functions. High-speed counting
normally single-phase 6 60KHz, or AB (Z) phase 2 60KHz + AB phase 1 10KHz. High-speed pulse is normally
8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz. Acceleration and deceleration are independent; the total of
high-speed co high-speed pulse cannot exceed 480KHz.
4. Support special encryption. Setting the password to 12345678 can completely prohibit reading programs.
[Note: Only 8-bit password encryption is supported]
5. Convenient wiring, using 3.5mm pitch pluggable terminals.
Production Information
Naming rules
FX3GC
1
2
3
4
5
6
7
-
8
9
11
10
Com ports
(optional)
High-speed counting
High-speed
pulse
Size
Single
phase
ABZ
phase
Output
Dimensions
(mm)
Normally
8 channels,
Y0-Y3 is 100KHz,
Y4-Y7 is 10KHz;
HSC + HSP
can not
exceed
480KHz.
90*65*32
Model
Digital
points
Analog
(optional)
DI DO
MAX
AI
MAX
AO
CAN
(2.0A/B)
MT: Y0-Y7 is MOS tube output, Y10-Y17 is transistor output; MR: relay output; MRT: mixed output.
Optional according to customer requirements.
FX3GC PLC User Manual
Installation size
Mechanical Design Reference
Filter function
High-speed counting
Input level
With filter function, the filter time can be set among 0-60ms,
defaulted as 10ms
Normally single phase 6 channels 60KHz or AB (Z) phase
2 channels 60KHz + AB phase 1 channel 10KHz
Passive NPN, common terminal isolation, S/S connected to 24V+
Digital relay output index
Max current
Load voltage
Circuit insulation
On response time
Mechanical life (no load)
Electrical life (rated load)
Output level
2A/point, 5A/8point COM
Below DC30V/ Below AC220V
Relay mechanical insulation
About 10ms
10 million times
300,000 times
Normally open dry contact output, COM can be connected to positive or negative
Digital transistor output index
Max current
Load voltage
Circuit insulation
Isolation voltage
(power supply-external terminal)
On response time
High-speed frequency output
Output level
MOS tube: 2A/point, 4A/4point COM, 5A/12point COM;
MT: 0.5A/point, 0.8A/4point COM, 1.6A/12point COM
DC24V
Optocoupler insulation
1500VAC
High-speed output: 10
μ
s, other 0.5ms
Normally 8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz
Low level NPN, COM connected to negative
Analog input index
Input signal
Response time
Analog input quantity
Accurary
1 scan cycle
0-8 Channel
12 bits
Analog output index
Output signal
Analog output quantity
Accurary
0-6 Channel
12 bits
External interface
Programming port
Environment
Operating temperature
Relative humidity
Storage temperature
Vibration frequency
0°C~50°C
5%~95%RH
-20°C~70°C
10-57Hz, amplitude 0.035mm; 57Hz-150Hz, acceleration speed 4.9m/s²
(10 times each on X, Y, Z, total 80 minutes each)
Comes with 2 programming ports: Mini B USB port
(faster download speed) and Rs232
2 Product structure
Diagram
1. 35mm rail installation
2. Terminal block for power input signal
4. Digital input display LED
5. Digital output display LED
8. PLC programming port
9. RUN/STOP PLC operation switch
10. Analog input (optional 485)
11. Analog output (optional CAN)
12. Digital input terminal block
7. Optional RS485
Diagram 1 Installation dimension drawing
Dimensions 90*65*32(mm)
Product structure
90
6
5
32
6
9
1
8
12
3
2
7
10
11
4
4
5
5
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
RUN
ERR
PWR
Y
Diagram 3 FX3GC-16MR/MT/MRT
◆
◆
◆
Electrical Design Reference
◆
Hardware interface
◆
Basic parameters
FX
C
3G -16M
8
8
FX
C
3G -30M
FX
C
3G -32M
16 14
16 16
N
o
n
e
Diagram 6 FX3GC-32MR/
MT/MRT
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
RUN
ERR
PWR
Y
10
11
12
13
14
15
16
17
10
11
12
13
14
15
16
17
Y
Diagram 5 FX3GC-30MR/
MT/MRT
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
RUN
ERR
PWR
Y
10
11
12
13
14
15
16
17
10
11
12
13
14
15
A
B
Y
Y
is the public terminal of switch output;
485/CAN
-
1P
-
1C1
-
A0
-
V
-
4DA
8AD
-
RT
M
16
3. Digital output terminal block
Terminal wiring specifications: 22-14AWG wire. The terminals of this series of models are all pluggable terminals.
For special model interfaces, please refer to the product silk screen.
other customization
0-5V/0-10V/-10~10V/-5~5V/0-20mA/4-20mA/other customization
Electrical parameters
Input voltage
DC 24V
Digital input index
Isolation mode
Input ON
Input resistance
Input OFF
Photoelectric coupling
High-speed input 3.3K
Ω
Common input 4.3
Ω
Electric current of high-speed input
is higher than 5.8mA/24V
Electric current of common input
is Higherthan 9.9mA/24V
Table 2 Electrical parameters
(
Continued from the table above)
Pin No.
Signal
Description
5
8
GND
TXD
Ground
Send
4
RXD
Receive
⑧
① ②
③ ④ ⑤
⑥ ⑦
Diagram 8 Optional
communication port
Table 1: Basic parameters
8
4
6
4
1
2
1
1
8
6
1
1
None
None
None
None
Electric current of high-speed input
is higer than 4.5mA/19V
Electric current of common input
is Higher than 4mA/17V
High-speed co high-speed pulse total does not exceed 480KHz
PT100/PT1000/thermocouple/NTC/0-10V/0-5V/-10~10V/-5~5V/0-20mA/4-20mA
◆
◆
◆
◆
Note: For detailed settings, please refer to "Coolmay CX3G&FX3GC Series PLC Programming Manual"
Diagram 7 RS232
programming port
RS232 programming port pin definition
GND is the common terminal of analog input/analog output
Diagram 4 FX3GC-16M
communication port/analog expansion
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
RUN
ERR
PWR
Y
A0
A
1
A
2
A
3
A4
A5
A6
A7
D
0
D
1
D
2
D
3
D4
D5
A
B
1
3
13. Mini USB programming port (faster download speed)
S
/
S
S
/
S
S
/
S
S
/
S
S
/
S
S
/
S
Note: S/S is the common terminal of digital input, which is connected to the positive pole of 24V;
GND
GND
A1
B1
H
L
(
)
※
485+ A
1
485- B
1
485+ A
485- B
H
L
~
AB phase
Normally
single
phase
6 channels
60KHz
Normally
AB phase
2 channel
60KHz+
1 channel
10KHz
Normally
ABZ phase
2 channel
60KHz
Installation size: DIN rail (35mm)
Refer to
【
Table 1: Basic parameters
】
COM
port
3
12
Comes with two programming ports:
Mini B-type USB port (faster download speed) and RS232 (8-pin mouse female socket)
16M can expand at most 2 RS485, 1 CAN port (2.0A/B), 6 inputs and 4 outputs analog
Or 1 RS485, 1 CAN port (2.0A/B), 8 inputs and 4 outputs simulation
Or 1 RS485, 8 inputs and 6 outputs analog
Or 2 RS485, 1 CAN port (2.0A/B)
1. Series: FX3GC: FX3GC series PLC
2. I/O points: 16: 8DI 8DO 30: 16DI 14DO 32: 16DI 16DO
3. Module M: Main Module
4. DO type: R: Relay; T: Transistor; RT: Relay and transistor mixed
5. AI 0-8 channels are optional
6. AO 0-6 channels are optional
7. AI type
V: 0 -10V V5: 0-5V V_: -10~10V V5_: -5~5V A0: 0-20mA A4: 4-20mA
8. AO type
V: 0-10V V5: 0-5V A0: 0-20mA A4: 4-20mA V_: -10~10V V5_: -5~5V
[Note: Optional negative voltage occupies two DA channels]
9. C1 means single-phase high-speed counting, C2 means AB phase counting, and C3 means ABZ phase counting.
Normally single phase 6 channels 60KHZ, or AB (Z) phase 2 channels 60KHz + AB phase 1 channel 10KHz.
10. P0 means 10KHz high-speed pulse, P means 100KHz high-speed pulse. High-speed pulse normally
8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz; acceleration and deceleration are independent; high-speed
co high-speed pulse total cannot exceed 480KHz.
11. COM port.
Refer to
【
Table 1: Basic parameters
】
PT: PT100 PT1000: PT1000 NTC: Thermistor (10K/50K/100K)
E: E type thermocouple (K type/T type/S type/J type can be customized, supporting negative temperature)
RS485
Communication port description
Serial port 1: RS422 (PLC programming port): Supports Mitsubishi programming port protocol,
which can be used to download PLC programs or communicate with devices that support
Mitsubishi programming port protocol.
Serial port 2: RS485 (AB port): Support Mitsubishi programming port protocol, Mitsubishi BD protocol,
RS protocol and Modbus RTU protocol.
※ Support RS, RS2, WR3A, RD3A, ADPRW instructions.
Serial port 3: RS485 (A1B1 port): Supports Mitsubishi programming port protocol, RS2 protocol and
Modbus RTU protocol.
※Support RS2, WR3A, RD3A, ADPRW instructions.
CAN port: supports RS2 protocol and Modbus RTU protocol.
※Support RS2, WR3A, RD3A, ADPRW instructions.