Chapter 7 Modbus mapping table
64
7.4 Read input memory
(
Func: 04
,
RW:R
)
NO(address)
Parameter
Description
Determination area
Unit
Factory
default
301001(03E8)
CH1 Current
value
Display measured value
Sensor type determines
input range
31000: OPEN
30000: HHHH
-30000: LLLL
℃
/
℉
-
301002(03E9)
CH1 Decimal
point
Depending on the type of
sensor selected
0
:
0
1
:
0.0
-
0
301003(03EA)
CH1unit
Temperature display unit
0:
℃
1:
℉
-
0
301004(03EB)
CH1 Set value
Set control temperature
SV Lower limit ~SV
Upper limit
℃
/
℉
0
301005(03EC)
CH1 Heating
_MV
Heating MV
0.0~100.0
%
-
301006(03ED)
CH1
Cooling_MV
Cooling MV
0.0~100.0
%
-
301007(03EE)
~301012(03F3)
CH2 parameter - same as above CH1
301013(03F4)
~301018(03F9)
CH3 parameter - same as above CH1
301019(03FA)
~301024(03FF)
CH4 parameter - same as above CH1
301025(0400)
CH1 LED(output)
0: OFF
1: ON
-
-
-
CH2 LED(output)
0: OFF
1: ON
-
-
-
CH3 LED(output)
0: OFF
1: ON
-
-
-
CH4 LED(output)
0: OFF
1: ON
-
-
-
-
Fixed to 0
-
-
-
-
Fixed to 0
-
-
-
-
Fixed to 0
-
-
-
-
Fixed to 0
-
-
-
-
Fixed to 0
-
-
-
-
Fixed to 0
-
-
301026(0401)
Unit
address
Unit address
01~31
-
01
301025(0400)address and data composition
Bit F
Bit E Bit D Bit C Bit B Bit A
Bit 9
Bit 8
-
-
-
-
-
-
DI-2 input DI-1outpu
t
0
0
0
0
0
0
0 or 1
0 or 1