Page 15
Option List Table
Option
Setting
0
Buttons Shown
0: Both mode and fan buttons show (default)
1: Show mode but fan button hidden
2: Show fan but mode button hidden
3: Both mode and fan buttons Hidden
Note: If the mode button is hidden, the service and
maintenance staff can turn the SMT-131 on or off by pressing
and holding the lower left of the LCD for 15 seconds. 2 chirps
indicate the SMT-131 has turned ON. 1 chirp indicates the
SMT-131 has turned off (ver 3.03+)
1
Permitted Modes
0: Off / Auto
1: Off / Auto / Heat / Cool
2: Off / Heat /Cool
3: Off / Heat
4 Off / Cool
5: Off / Auto (Display current heating or cooling mode)
2
Room / Set display
0: Show room and set temp (default)
1: Show set temp only
3
Native display format
0: C (default)
1: F
4
C/F button shown on LCD
0: Off(default)
1: On
5
High temp set limit
5C-30C or 41F-86F
6
Low temp set limit
5C-30C or 41F-86F
7
Dead band
0C-5.0C or 0F-10.0F in 0.1C/0.1F steps.
Depending on Option 3 above.
Data format: Dead band * 10
8
Fan Purge Period
0: OFF
1: Fan purge - 1 min
2: Fan purge - 3 min
3: Fan purge - 5 min
4: Fan purge - 10 min
5: Heat only fan purge - 1 min
6: Heat only fan purge - 3 min
7: Heat only fan purge - 5 min
8: Heat only fan purge - 10 min
9: Cool only fan purge - 1 min
10: Cool only fan purge - 3 min
11: Cool only fan purge - 5 min
12: Cool only fan purge - 10 min
9
Fan span
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
10
0-10V Fan Interval (PI)
10-300 seconds 10 seconds' steps (60 seconds default)
11
0-10V Fan direction
0: 0 - 10V
–
slow to fast (Forward Acting)
1: 10 to 0V
–
slow to fast (Reverse Acting)
12
0-10V Fan minimum value
(Starting fan voltage when
running)
0 -10V
Data format: 0-10V Fan minimum value * 10