ASCII I/F
CoolMasterNet PRM Rev 0.7
43
www.coolautomation.com
© 2017 CoolAutomation
L1.300 -
L1.301 +
L1.302 -
L2.100 ?
L2.101 ?
L2.102 ?
L2.103 ?
OK
Unset main RC: Indoor Unit 206 on line L2
>
main L2.206 0
OK
Set new main RC: Indoor Unit 201 on line L2
>
main L2.201 1
OK
vam
SYNOPSIS
> <a|b|x|n|l|L|h|H|s|t|A|+|->
vam
vam <
>
DESCRIPTION
Control Ventilation Unit.
·
vam
<UID_STRICT>
- get Ventilation Unit status.
·
vam - get all Ventilation Units status.
Letter
Operation
Compatibility
DK
ME
LG
SM
a
Auto Mode
P
P
P
P
b
Bypass (Bps) Mode
P
P
P
x
Heat Exchange (HExc) Mode
P
P
P
P
n
Normal Mode
P
S
Sleep Mode
P
l
Low Fan
P
P
P
P
L
Low Fan with Fresh-Up
P
h
High Fan
P
P
P
P
H
High Fan with Fresh-Up
P
s
Super High Fan
P
P
t
Top Fan
P
A
Auto Fan
P
P
+
Turn on ventilation unit*
P
-
Turn off ventilation unit*
P
ON/OFF control of the Ventilation Unit is performed with regular
There are, though, dual units, that consist of Air Condition Unit and Ventilation unit. In this case
commands will control the Air Condition Unit, while vam <
> - will
control the Ventilation Unit.
EXAMPLE
Set Heat Exchange mode on Ventilation Unit 101 on Line L1
>
vam L1.101 x