Commands Reference
CoolMaster PRM
24
www.coolautomation.com
© 2015 Cool Automation LTD
Rev 4.08
Only CoolMaster 1000D
v 2.6.9
4.1.21 group
SYNOPSIS
group [<UID_MASTER> <UID>] | delall
DESCRIPTION
Without parameters group command will list current groups. With delall parameter command will
delete all groups. In format with two UID's command will group two units. First unit is a master, second
unit will follow all settings of the master unit. Grouping will take effect only after power reset of
CoolMaster.
EXAMPLE
>group 101 102
OK
Group units 1-01 and 1-02. Unit 1-02 will
follow all settings of the 1-01 unit.
>group
101-->101
102-->102
OK
List groups
group delall
Delete all groups
EXIT CODE
OK
Request Successfully Executed
ERROR:1
Unit with specified UID not found
COMPATIBILITY
CoolMaster 1000D
v 2.4.4
CoolMaster 2000S
v 2.4.4
CoolMaster 3000D
v 2.4.4
CoolMaster 4000M
v 2.4.4
CoolMaster 6000L
N.A.
CoolMaster 7000F
N.A.
CoolMaster 8000I(MH)
N.A.
CoolMaster 9000H
N.A.
CoolMaster G
any
Before v2.5.6 number of groups is limited to 4. Beginning from v2.5.6 number of groups is limited to 20.
4.1.22 vam
SYNOPSIS
vam <UID> a|b|x|l|L|h|H|s|A
DESCRIPTION
This command controls VAM (Ventilation) HRV unit mode and fan speed.
Letter
Compatibility
1000D(DK)
4000M(ME)
6000L(LG)
a - Auto Mode
P
P
P
b - Bypass (Bps) Mode
P
P
x - Heat Exchange (HExc) Mode
P
P
P
n - Normal Mode
P