background image

1

P000283-001

VFRSC IO&M

This publication contains installation, operation and main-

tenance instructions for the standard 

Vari-Flow

®

 Remote 

Speed Controller.

Carefully read this publication prior to any 

installation or maintenance procedure.

Any additional publications can be obtained from Loren 

Cook Company through any of the following:

•  lorencook.com

•  [email protected]

•  417-869-6474 ext. 166

For information and instructions on special equipment, con-

tact Loren Cook Company Customer Service Department at 

417-869-6474.

Storage

If the controller is stored for any length of time prior to instal-

lation, store controller in the original packaging inside from the 

weather and keep temperature between -22°F to 122°F (-30°C 

to 50°C).

Installation

The VFRSC can be mounted in a electrical box with the two 

screws provided. This device requires a 24VAC/DC power 

supply. VFRSC is UL Listed when mounted in UL Listed en-

closure. Minimum transformer output of 1VA.

Location and Maintenance

Consider the following points while choosing a location for 

the Vari-Flow Remote Speed Controller.
•  Less than 100 feet of wiring to motor or to VFABK.

•  Install the controller indoors.

• 

Do not place the controller on the floor.

•  Maintain a temperature between 30°F to 110°F (-1°C to 

43°C). A temperature beyond this range may cause conden-

sation and sweating of metal parts.

•  Maintain a low humidity, dry, and clean atmosphere. Ensure 

that the controller is not in the path of blowing dust, rain, or 

snow.

Operation

This device outputs a 0-10v signal voltage. The dial does not 

indicate voltage, but a range of available voltage from max to 

min. Vari-Flow motors operate on a 2-10V signal. Below 2V, 

the motor stops but is still powered. 

®

REMOTE SPEED CONTOLLER

Vari-Flow

®  

VFRSC

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Wiring

All wiring should be in accordance with local ordinances and 

the National Electrical Code, NFPA 70. Ensure the power sup-

ply (voltage, frequency, and current carrying capacity of wires) 

is in accordance with the motor nameplate. When paired with 

Air Balance Kit (VFABK), see Air Balance Kit supplemental in-

stallation instructions for wiring.

0-10VDC

24VAC/DC

Common

Remote Speed Controller

Отзывы: