SPECIFICATIONS
Performance Specifications
• Input Voltage: (120*)(208)(208/120)(220)(240)(240/120)(347)(480)(600) VAC. *120 VAC up to 5500 VA.
• Input Voltage Range: +12% to -15% at full load without battery usage. Note: For input voltage excursions within
+12 to -50%, UPS will incorporate Adaptive Input Range control, in conjunction with the load percentage, to
accept this range without using battery, still maintaining specified output voltage regulation.
• Input Frequency Range: 57 Hz to 63 Hz. Generator compatible.
• Input Power Factor: Self corrected to >.98 (approaching unity).
• Input Current Harmonics: < 5% THD (Total Harmonic Distortion).
• Output VA Rating: (4500) (5500) (6500) (7500) (8300) (9000) (10000) (11000) (12000) (13500) (14500)
(15500) VA.
• Output Voltage: (120*)(208/120)(240/120)(240/208/120**) VAC. *120 VAC up to 5500 VA.
**Full rated load from a single 120VAC output (4500 VA through 11000 VA)
• Output Voltage Distortion: Sinewave with less than 3% THD under linear load.
• Output Frequency: 60 Hz +/- 0.5% under full load during battery mode of operation.
• Voltage Regulation: +/- 1.5%, no load to full load.
• Output Power Rating: VA at 0.90 power factor. VA x PF = Watts.
•
Battery Time: Battery run times are specified at full rated output watts.
• Battery Type: Integral, valve regulated, sealed lead calcium, maintenance free with 10 year design life.
• Charger Type: Integral, 4 stage, temperature compensated.
• Charger Ratings: 5 amp for battery options A and B and all 6500VA units. 10 amp for battery options C through J.
• Recharge Time: <10 times the discharge period to 90% capacity.
• DC Bus Voltage: 120 VDC
• Overload Rating for system: 125% for 2 minutes, 150% for 30 seconds, 200% for 15 cycles when fed from an AC
power source.
• On Battery Overload Rating: 125% for 30 cycles, 150% for 3 cycles.
• Common Mode Attenuation: 70 dB minimum (models with internal shielded isolation transformer).
• Transverse Mode Attenuation 60 dB minimum at 100KHz (models with internal shielded isolation transformer).
• Reactive Power Correction: Load @ .6PF automatically corrected to >.98 at input.
•
Efficiency: 87% at full load typical.