Contents
Section
Description
Page
1.0
Description & Installation
2
2.0
Operation
3
3.0
Maintenance
5
4.0
Troubleshooting
5
5.0
Warranty
5
Pilot Pressure
Atmospheric Pressure
Supply Pressure
Output Pressure
441-622-015
Type 500X
Page 1
Electropneumatic Transducer (I/P, E/P)
Installation, Operation and
Maintenance Instructions
Type 500X
Ordering Information
Type 500X I/P Transducers
Output Range
Part Number
Input
psi
kPa
Impedance
500-AA
4-20 mA
3-9
20-60
90 Ohms
500-AB
4-20 mA
9-15
60-100
90 Ohms
500-AC
4-20 mA
3-15
20-100
180 Ohms
500-AD
4-20 mA
3-27
20-185
220 Ohms
500-AE
4-20 mA
6-30
40-200
220 Ohms
500-AF
4-20 mA
1-17
7-117
250 Ohms
500-BC
10-50 mA
3-15
20-100
70 Ohms
500-BD
10-50 mA
3-27
20-185
85 Ohms
500-BE
10-50 mA
6-30
40-200
85 Ohms
500-AG
4-20 mA
2-60*
14-420
225 Ohms
500-AH
4-20 mA
3-120*
20-830
260 Ohms
500-BF
0-60 mA
2-120*
15-830
220 Ohms
Type 500X E/P Transducers
Output Range
Part Number
Input
psi
kPa
Impedance
500-CC
0-5 VDC
3-15
20-100
615 Ohms
500-CD
0-5 VDC
3-27
20-185
530 Ohms
500-CE
0-5 VDC
6-30
40-200
530 Ohms
500-DC
1-9 VDC
3-15
20-100
985 Ohms
500-DD
1-9 VDC
3-27
20-185
840 Ohms
500-DE
1-9 VDC
6-30
40-200
840 Ohms
500-CF
0-5 VDC
2-60*
14-420
500 Ohms
500-EH
0-10 VDC
3-120*
20-830
805 Ohms
*Output shown is as calibrated at the factory. Large span adjustment capability
allows recalibration to achieve output ranges from 3-35 psig (20-240 kPa) with 2-