![Control Techniques Unidrive M300 Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/control-techniques/unidrive-m300/unidrive-m300_quick-start-manual_2658696001.webp)
Unidrive M300 Quick Start Guide
1
Issue Number: 1
This guide is intended to provide basic information required in order to set-up a drive to run a motor.
Please refer to the
Unidrive M300 User Guide
which is available to download from
www.controltechniques.com/userguides.
1
Safety information
2
Product information
2.1
Ratings
Unidrive M300
Quick Start Guide
This guide does not include safety information. Incorrect installation or operation of the
drive, could cause personnel injury or equipment damage. For essential safety
information, please refer to the
Unidrive M300 User Guide
or the safety booklet supplied
with the drive.
Model
Input
phases
Max.
cont
input
current
Max input
fuse rating
Nominal cable size
Output current
European
USA
1 Ph
3 Ph
Input
Output
Input
Output
Max.
cont
output
current
Nominal
power
Motor
power
ph
A
A
A
mm
2
mm
2
AWG
AWG
A
kW
hp
01100017
1
10
1
1
16
16
1.7
0.25
0.33
01100024
1
16
1
1
14
16
2.4
0.37
0.5
01200017
1
6
1
1
16
16
1.7
0.25
0.33
01200024
1
6
1
1
16
16
2.4
0.37
0.5
01200033
1
10
1
1
16
16
3.3
0.55
0.75
01200042
1
16
1
1
16
16
4.2
0.75
1
02100042
1
18.8
20
2.5
1
12
16
4.2
0.75
1
02100056
1
24
25
4
1
10
16
5.6
1.1
1.5
02200024
1 / 3
5.3/4.1
6
6
1
1
16
16
2.4
0.37
0.5
02200033
1 / 3
8.3/6.7
10
10
1
1
16
16
3.3
0.55
0.75
02200042
1 / 3
10.4/7.5
16
10
1
1
16
16
4.2
0.75
1
02200056
1 / 3
14.9/11.3
20
15
2.5/1.5
1
12/14
16
5.6
1.1
1.5
02200075
1 / 3
18.1/13.5
20
15
2.5
1
12
16
7.5
1.5
2
02400013
3
2.4
6
1
1
16
16
1.3
0.37
0.5
02400018
3
2.9
6
1
1
16
16
1.8
0.55
0.75
02400023
3
3.5
6
1
1
16
16
2.3
0.75
1
02400032
3
5.1
6
1
1
16
16
3.2
1.1
1.5
02400041
3
6.2
10
1
1
16
16
4.1
1.5
2
03200100
1 / 3
23.9/17.7
25
20
4
1.5
10/12
14
10
2.2
3
03400056
3
8.7
10
1
1
14
16
5.6
2.2
3
03400073
3
12.2
16
1.5
1
12
16
7.3
3
3
03400094
3
14.8
16
2.5
1.5
12
14
9.4
4
5
04200133
1 / 3
25
20
4/2.5
2.5
10
12
13.3
3
3
04200176
3
25
4
2.5
10
12
17.6
4
5
04400135
3
20
2.5
2.5
10
12
13.5
5.5
7.5
04400170
3
25
4
2.5
10
12
17
7.5
10
The nominal cable sizes shown in the table above, are provided as a guide only. Ensure
that the cables used conform to the local wiring regulations.
WARNING