8.6 I/O
Capacity
5000 Series I/O
Expansion
Capacity
Maximum 40 I/O modules with a further limitation of 16
modules of any one type.
512 digital inputs using 32 point digital output modules
512 digital inputs using 32 point digital input modules
128 analog inputs using 8 point analog input modules
64 analog outputs using 4 point analog output modules
32 counter inputs using 4 point counter input modules
Example: 16 of the 32 point digital output m 16 of
the 32 point digital input m 8 of the 8 point analog
input modules would yield an expansion of 1088 I/O points.
8.7 Digital
Inputs
Input Points
4 Digital Input/Counter, opto coupler isolation
Digital Input,
Counter
24Vrms/30V maximum input
10Vrms/10V minimum ON input
2V maximum OFF input
Typical threshold voltage is 4 to 6V
Typical input hysteresis 1.0V
Typical input current
2.5mA at 10V
7mA
at
24V
Counter Input
Frequency
(Counter 0, 1, 2)
5 kHz maximum with filter OFF
30 Hz maximum with filter ON
Counter Input
Frequency
(Counter 3)
500 Hz maximum
Transient
Protection
Transient: 2.5kV surge withstand capability as per ANSI/IEEE
C37.90.1-1989
8.8 Digital
Outputs
Status Output
Opto coupler open collector transistor
30V, 60mA
opens on fault
Transient
Protection
Transient: 2.5kV surge withstand capability as per ANSI/IEEE
C37.90.1-1989
8.9
Approvals and Certifications
Safety
Non-Incendive Electrical Equipment for Use in Class I, Division
2 Groups A, B, C and D Hazardous Locations.
Digital
Emissions
FCC Part 15, Subpart B, Class A Verification
EN50081-2: 1993 Electromagnetic Compatibility Generic
Emission Standard Part2: Industrial Environment
Immunity
EN61000-6-2: 1999 Electromagnetic Compatibility Generic
Standards Immunity for Industrial Environments
Declaration
This product conforms to the above Emissions and Immunity
Standards and therefore conforms with the requirements of
Council Directive 89/336/EEC (as amended) relating to
SCADAPack 32P Controller Hardware Manual
May 26, 2006
39