INPUTS

OUTPUT

Eight digital inputs coming from SPST contacts can be wired to terminals 7-14.

Common return for contacts at terminal 6.

Using electronic switches, terminal 6 is the positive leg.

In order to avoid false triggering, contacts will be considered closed or open after

3 seconds from stable condition.

Modifying the configuration by means of GsmSuite, either in local or remote mode

it will be possible to change:

Debounce time from 1 to 99 seconds.

Enable and disable input closing detection.

Enable and disable input opening detection.

Contact voltage < 20 V

Contact current < 2 mA

9 x 2.5 mm (AWG14) screw connector

Process or appliance can be controlled by means of 1 SPST relay contact

available between terminals 3-4.

Rated current 4 A

Rated voltage 250 Vac

Max breaking capacity 2500 VA

Minimum contact load 100 mA, 12 V

Cadmium free contacts

Insulation 250 V (IEC60664 / VDE0110b - cat. III / C)

Surge voltage coil contacts: 4000V

Dielectric strength coil-contacts 2500V

open contact circuit 1000V

4 x 2.5 mm (AWG14) screw connector

¡

¡

¡

DC

RMS

RMS

RMS

2

2

DECLARATION OF CONFORMITY

R&TTE Directive 1999/5/EC

Manufacturer: Contrive, Srl

Via Enrico Fermi 18 24040 Suisio Italy
Brand:

Contrive

Equipment name:G / Gp

Equipment type: GSM/GPRS modem

EMCC DR. RAŠEK, GmbH

Moggast, Boelwiese 5

91320 Elbermannstadt Germany

Company identification:

Product identification:

We declare on our sole responsibility, that the product described above

is in compliance with the essential requirements of the 1999/5/CE Directive:

EN 301 489-1

EN 301 489-7

EN 61326

EN 55024

EN 300 607

and all tests were carried out
Notified Body:

Health and safety requirements pursuant to clause 3.1a:

Protection requirements concerning EMC clause 3.1b:

Measures for the efficient use of the radio frequency spectrum clause 3.2:

EN 301 511

EN 60950-1

GSM900/1800 essential requirements for mobile stations

Safety of information technnology equipment

Electromagnetic compatibility
ElectroMagnetic compatibility and Radio spectrum Matters

Specific conditions for mobile and portable radio and ancillary equipments
ElectroMagnetic compatibility measurement, control and laboratory use
Information technology equipment - Immunity characteristics

Radio spectrum matters

NOTE:

Class B equipment (domestic) emission level applied.

Class A equipment (industrial) immunity level applied.

Suisio, Italy February 21, 2006

¡

¡

¡

CONTRIVE RESERVES THE RIGHT TO MODIFY THE CHARACTERISTICS STATED

IN THIS INSTRUCTION MANUAL AT ANY TIME AND WITHOUT PRIOR NOTICE.

© COPYRIGHT 2002...2005 CONTRIVE SRL ITALY. ALL RIGHTS RESERVED.

GA

GX

The embedded antenna is located under the front panel. This omnidirectional

antenna can work properly if the front side of the device is not shielded by metallic

frames (i.e.: the GsmA is installed inside a metal cabinet).

An external dual-band antenna must be connected to the RF interface, implemented

as a 50 FME male coaxial jack at the end of a short RG174 cable stub exiting from

the top side of the device. The antenna must fulfil the requirements given below:

We recommend a VSWR max of 1.5:1 although a VSWR max of 2:1 can be accepted

without affecting performance and certification.

The DC impedance is floating but there is no problem when using antennas that

present a short to ground.

W

CONTRIVE S.R.L.

Via Enrico Fermi 18 I-24040 SUISIO (Bergamo)

Tel. +39 (0)35 4948236 Fax +39 (0)35 4933759

B1018.EN / 0211

www.gsm-control.biz

Dual band EGSM900 and GSM1800 for data, sms, fax and voice applications

Full Type Approved and compliant with ETSI GSM Phase 2+
Output power:

Class 4 ( 2W @ 900 MHz )

Class 1 ( 1W @ 1800 MHz )

Temperature:

operating -20 to 55°C

storage and transport –30 to 85°C

Relative humidity:

operating 5 to 95% non-condensing

storage & transport 5 to 95% condensation allowed outside

Enclosure:

EN-50022 rail 4 modules, polycarbonate, UL94 -V0

Overall dimensions: mm 71 x 90 x 58 ( W x H x D )
Weight:

200 g

Degree of protection: IP 40 (

IEC 529) properly fitted

EN-60529 /

Power supply:

12 V DC ±20% polarity independent

12 V AC ±20%

< 30 mA @ 12 V DC in standby mode

< 100 mA @ 12 V DC in standby mode, relays ON

< 200 mA @ 12 V DC in communication mode

<

1 A @ 12 V DC max peak current

2 x 2.5 mm (AWG14) screw connector

This unit can be supplied either by alternating or direct current, polarity

independent. Power supply connection on terminal 1 and 2, top right side.

The power supply unit must meet the demands placed on SELV [1] circuits in

accordance with EN60950.

The power supply must not be shared with other equipment: suggested power

supply source is a simple 12VAC / 5VA transformer.

The maximum permissible connection length between device and supply source

is 3 m. Overvoltages are suppressed by internal varistor.
[1] Safety Extremely Low Voltage

2

This device should be installed only by qualified personnel. Carefully read the

instruction manual in its entirety and keep it safe for future reference.

It is essential to know the information and comply with the instructions given in the

manual to ensure the fitting is installed, used and serviced correctly and safely.
This RF unit is not designed for and intended to be used in portable applications

(within 20 cm or 8 inches of the body of the user) and such uses are strictly prohibited.
This unit is not authorised for use as critical component in life-support devices or

systems unless a specific written agreement has been given.
If incorrectly installed in a vehicle, the operation of GSM device could interfere with

the correct functioning of vehicle electronics. Verification of the protection of vehicle

electronics should form a part of the installation.

Regulations must be considered to operate a vehicle’s light or horn on public roads.
No complex software or hardware system is perfect.

Bugs are always present in a system of any size.
In order to prevent danger to life or property, it is the responsibility of the system

designer to incorporate redundant protective mechanism appropriate to the risk

involved.
All units are 100% functionally tested. Specifications are based on characterisation

of tested sample units rather than testing over temperature and voltage each unit.
Contrive disclaims all liability for damage to the fitting or to other property or persons

deriving from installation, use and maintenance that have not been carried out in

conformity with this instruction manual, which must always accompany the fitting.

The G is an industrial DIN rail GSM modem for the supervision and control

of remote inputs and outputs by means of enhanced features available through GSM

network.

Industrial standard interface and an integrated SIM card reader mean it can be used

rapidly, easily and universally to quickly implement new applications in telemetry,

telematics and remote control. All interfaces are integrated in the housing.

The connections are suitable for use in domestic and industrial environments.

DIMENSIONS [mm]

SAFETY INFORMATION

PRODUCT FEATURES

ANTENNA

PRODUCT DESCRIPTION

58

90

71

r

If the device has been stored in a cold environment, then condensation can

occur. Before starting operations, the device must be absolutely dry.

Thus, an acclimatization period of at least three hours must be observed.

In order to avoid possible damage, we recommend that you only use the

specified accessories.

These have been tested and shown to work well with this unit.

i

Do not install this unit near medical devices like pacemakers or hearing

aids. This unit may interfere with the operation of these devices.

Switch off this unit when flying.

Secure it so that it cannot be switched on inadvertently.

Do not install this unit near petrol stations, fuel depots, chemical plants or

blasting operations when this unit can disturb the operation of technical

equipment.

Interference can occur if this unit is used near televisions, radios or

personal computers.

BUILT ON PROVEN TECHNOLOGY

POWER SUPPLY

INPUTS / OUTPUT

Frequency TX
Frequency RX
Impedance

VSWR

TX max

RX max

Polarization
Typical gain

880 to 915 MHz
925 to 960 MHz

50 ohms
1.5 : 1
1.5 : 1

Linear
0 dBi in one direction at least

1710 to 1785 MHz
1805 to 1880 MHz

1 2 3 4 5 6 7 8

INSTALLATION

This unit can be installed on any standard EN-50022 rail by simple snap-in.

A minimum protection degree IP40 must be guaranteed, raised to IP54 for open-

air application.

A. Power Supply input

2 x 2,5mm (AWG14)

B. Input and output terminals

12 x 2,5mm (AWG14)

C. Input red led status indicators

D. Output green led status indicator

X. External antenna (type X only)

RG174 + FME male jack

S. GSM operation LED indicator

OFF

No power supply
ON

Module switched ON

Not registered on the network,

missing SIM or invalid PIN
SLOW FLASH

Module switched ON

Registered on the network
QUICK FLASH

Module switched ON

Registered on the network

Communication in progress

2

2

¡

¡

¡

¡

PERMANENTLY

200ms ON / 2s OFF

200ms ON / 600ms OFF

à

õ

õ

X

A

B

1

13

12

11

10

9

8

7

6

5

4

3

2

14

S D

C

Your GsmAlarm is the product of advanced engineering, design and craftmanship

and should be treated with care. The suggestion below will help you to enjoy this

product for many years.

Both fixed and mobile applications are allowed, as defined below:

means that the device is physically secured at one location and is not able

to be easily moved to another location.

means that the device is designed to be used in other than fixed locations

and generally in such a way that a separation distance of at least 20 cm (8 inches)

is normally maintained between the transmitter’s antenna and the body of the user

or nearby persons.

Do contact an authorized service center in the unlikely event of a fault in the unit.

¡

¡

¡
¡

¡
¡

¡

¡

¡

¡

Do not expose the unit to any extreme environment where the temperature or

humidity are out of operating range.
Do not use or store the unit in dusty or dirty areas. Its moving parts (SIM holder for

example) can be damaged.
Do not use chemical cleaning agent on the unit or the SIM card.
Do not attempt to disassemble the unit or remove any part or label.

There are no user serviceable parts inside.
Do not expose the unit to water, rain or spilt beverages. It is not waterproof.
Do not abuse the unit by dropping, knocking or violenty shaking it.

Rough handling can damage it.
Do not place the unit alongside computer discs, credit or travel cards or other

magnetic media. The information contained on these devices may be affected.
This unit is under your responsibility. Please treat it with care respecting all local

regulations. It is not a toy. Therefore, keep it in a safe place at all times and out of

the reach of children.
Treat the SIM card with the same care as your credit card: do not bend or scratch

or expose it to static electricity.
Try to remember your unlock and PIN codes. Become familiar with and use the

security features to block unautorised use and theft.

Fixed

Mobile

CARE AND MAINTENANCE

0678

1018.01.00 GA
1018.02.00 GA
1018.01.01 GX
1018.02.01 GX
1018.01.10 GpA
1018.02.10 GpA
1018.01.11 GpX
1018.02.11 GpX

EMBEDDED ANTENNA
EMBEDDED A BACKUP BATTERY
EXTERNAL ANTENNA
EXTERNAL A BACKUP BATTERY
EMBEDDED ANTENNA
EMBEDDED A BACKUP BATTERY
EXTERNAL ANTENNA
EXTERNAL A BACKUP BATTERY

B

B

B

B

G

GSM REMOTE MONITOR

GSM/GPRS REMOTE MONITOR

Gp

USER GUIDE

1 2 3 4 5 6 7 8

THE INFORMATION CONTAINED IN THIS DOCUMENT ARE SUBJECT TO CHANGE

WITHOUT NOTICE. PRODUCT NAMES, CORPORATE NAMES OR TITLES USED WITHIN

THIS DOCUMENT MAY BE TRADEMARKS OR REGISTERED TRADEMARKS OF OTHER

COMPANIES AND ARE MENTIONED ONLY IN AN EXPLANATORY MANNER TO THE

READERS’BENEFIT,AND WITHOUT INTENTION TO INFRINGE.
WHILE EVERY EFFORT HAS BEEN MADE TO MAKE SURE THE INFORMATION IN THIS

DOCUMENT IS CORRECT, CONTRIVE CAN NOT BE LIABLE FOR ANY DAMAGES

WHATSOEVER FOR LOSS RELATING TO THIS DOCUMENT.

WARRANTIES

CONTRIVE GUARANTEES FOR TWO YEARS FROM THE DATE OF MANUFACTURE OF

ITS PRODUCT TO REPLACE, OR, AT ITS OPTION, TO REPAIR ANY PRODUCT OR PART

THEREOF WHICH IS FOUND DEFECTIVE IN MATERIAL OR WORKMANSHIP OR WHICH

OTHERWISE FAILS TO CONFORM TO THE DESCRIPTION OF ITS SALES ORDER.

CONTRIVE MAKES NO WARRANTY OF MERCHANTABILITY OR ANY OTHER

WARRANTY EXPRESS OR IMPLIED. IN NO EVENT SHALL CONTRIVE BE LIABLE FOR

CONSEQUENTIAL OR SPECIAL DAMAGES OF ANY NATURE WHICH MAY ARISE IN

CONNECTION WITH SUCH PRODUCTS.

THE WARRANTY DOES NOT APPLY IN CASE OF IMPROPER USE

Отзывы: