Introduction
515 HC04 - 8 June 2007
5
Isolated Outputs
The opto-isolated outputs can re-transmit any main menu variable. The type
of output is determined by the nature of the assigned variable. Totals are
output as pulses and rates are output as 4-20mA signals. One output is
standard, a second output is available as an option.
Relay Outputs
The relay alarms can be assigned to any of the main menu variables of a rate
type. The alarms can be fully configured including hysteresis. Two relays
are standard with an additional two available in the advanced option.
Software Configuration
The instrument can be further tailored to suit specific application needs
including units of measurement, custom tags, second language or access
levels. A distributor can configure these requirements before delivery.
Instrument parameters including units of measurement can be programmed
in the field, according to the user access levels assigned to parameters by the
distributor.
All set-up parameters, totals and logged data are stored in non-volatile
memory with at least 30 years retention.
Temperature Input Types
Temperature sensor inputs can be either PT100, PT500, 4-20mA, 0-5V or
1-5V signals.
Figure 1 Typical Application Diagram
T
Feed Flow
Temperature
Transmitters
Analog
Input 1
Return Flow
Analog
Input 2
T
Energy
Load
DP Meter
Analog
Input 3
Hi Flow
Analog
Input 4
Option
Содержание 515
Страница 4: ...iv 515 HC04 8 June 2007 ...
Страница 8: ...viii 515 HC04 8 June 2007 ...
Страница 16: ...Introduction 8 515 HC04 8 June 2007 ...
Страница 60: ...Instrument Calibration 52 515 HC04 8 June 2007 ...
Страница 80: ...Communications 72 515 HC04 8 June 2007 ...
Страница 82: ...74 515 HC04 8 June 2007 ...
Страница 88: ...80 515 HC04 8 June 2007 ...