Installation & Maintenance
12
515 FA01 - 29 August 2021
Terminal Wiring Insulation
Terminals 1-30 are all rated at <35Vdc and wiring with basic insulation is
adequate.
Use copper conductors only.
Relay Wiring
Relay terminals are 31-35 or 31-36 depending on the version of option card
fitted. When controlling circuits operate at mains voltages, or voltages
>35Vdc, it is necessary to use UL/CSA approved cabling with
supplementary insulation and a current capacity suitable for the connected
circuit. Use copper conductors only. The maximum current must be <5A as
stated in sec 2.
Where circuits >35Vdc are connected UL/CSA approved cabling with
supplementary insulation. 0.75mm², 6A current capacity is sufficient.
Mains Power Wiring
Only use UL/CSA approved cabling with supplementary insulation and
copper conductors. A minimum cable cross section area of 0.75mm² (18
AWG) is required. However, this must be selected with respect to the
installed over-current protection device and in accordance with the local
relevant Electrical Code of Practice as dictated by the Authority Having
Jurisdiction (AHJ).
The terminal designations (L/N/E) are clearly indicated just above the mains
input connector on the rear panel of the instrument.