CONTINENTAL CONTROL SYSTEMS RWNB-3D-240-P Скачать руководство пользователя страница 9

9

Install the CTs around the conductor to be measured and connect the CT leads to the meter. 

Al-

ways turn off power before disconnecting any live conductors.

Split-core CTs can be opened for installation around a conductor. A nylon cable tie may be se-
cured around the CT to prevent inadvertent opening. If using solid-core CTs, put the line conduc-
tors through the CTs as shown i

Figure 1

 above.

CTs are directional. If they are mounted backwards or with their white and black wires swapped the 
measured power will be negative. The status LEDs indicate negative measured power by flashing 
red.

When installing WattNode Revenue models, be sure to only use IEEE C57.13 class 0.6 current 
transformers, such as the Accu-CT; other CTs are less accurate and may not provide revenue ac-
curacy. Contact sales for more information on appropriate CTs.

3.4.1  CT Wiring

The current transformers connect to the six position black screw terminal block. Connect the 
white and black CT wires to the meter terminals marked 

Ø

A CT

Ø

B CT

 , and 

Ø

C CT

 (see 

Figure 1

 

above). Excess length may be trimmed from the wires if desired. Connect each CT with the white 
wire aligned with the white dot on the label, and the black wire aligned with the black dot. Note 
the order in which the phases are connected, as the line voltage phases 

must

 match the current 

phases for accurate power measurement.

3.5  Connect the Output Signals

 

The meter outputs are electrically isolated from dangerous voltages.

 

If the output wiring is near line voltage wiring, use wires or cables with a 300 V or 600 V rating 
(not less than the service voltage).

 

If the output wiring is near bare conductors, it should be double insulated or jacketed.

 

You may install two wires into each screw terminal by twisting the wires together, inserting 
them into terminal, and securely tightening. Note: a loose wire can disable an entire network 
section. 

 

Use shielded twisted-pair cable to prevent interference. If there is no common conductor, con-
nect the shield to the 

terminal.

3.5.1  WattNode Pulse Outputs

Use the following directions when connecting the pulse outputs of a WattNode Pulse meter.

 

The outputs 

P1

P2

, and 

P3

 should not be connected to negative voltages, or to voltages 

greater than +60 Vdc. For reliable operation, limit the current to 5 mA.

 

For long distances, use shielded twisted-pair cable to prevent interference. With shielded 
cable, connect the shield to earth ground at one end.

 

If you need to add pull-up resistors to limit current, see th

Operating and Reference Guide

.

The WattNode pulse outputs may be connected to most devices that expect a contact closure or 
relay input. See th

Operating and Reference Guide

 for more complex connection information.

Common (or GND)

Input (Positive)

Monitoring Equipment 

or Display

Input (Positive)

Input (Positive)

P1

P2

P3

COM

O

u

tp

u

t

W

ATT

N

ODE

The following table shows the pulse output channel assignments for the standard bidirectional 
outputs and for optional output configurations. See the website article 

WattNode Pulse - Options

 

for more details on available options. 

Содержание RWNB-3D-240-P

Страница 1: ...allation Manual WattNode Pulse Models WattNode Revenue Pulse Models WNB 3Y 208 P RWNB 3Y 208 P WNB 3Y 400 P RWNB 3Y 400 P WNB 3Y 480 P RWNB 3Y 480 P WNB 3Y 600 P RWNB 3Y 600 P WNB 3D 240 P RWNB 3D 240 P WNB 3D 400 P RWNB 3D 400 P WNB 3D 480 P RWNB 3D 480 P ...

Страница 2: ...rent Transformers 8 3 5 Connect the Output Signals 9 4 Operation 10 4 1 Initial Configuration 10 4 2 Power Status LEDs 10 4 3 Monitoring 11 4 4 Pulse Scale Factors 11 4 5 Maintenance and Repair 12 5 Specifications 12 5 1 Accuracy 12 5 2 Measurement 13 5 3 Electrical 13 5 4 Pulse Outputs 14 5 5 Certifications 14 5 6 Environmental 15 5 7 Mechanical 15 5 8 FCC Information 15 5 9 Warranty 16 5 10 Limi...

Страница 3: ...rnings and precautions before installing and using the product Potential Shock Hazard from Dangerous High Voltage Functional ground should be connected to earth ground if possible but is not required for safety grounding UL Listing mark for U S A and Canada FCC Mark This logo indicates compliance with part 15 of the FCC rules Complies with the regulations of the European Union for Product Safety a...

Страница 4: ...0 ØA and ØB 1 Phase 2 Wire 240V no neutral n a 166 276 3D 240 ØA and ØB 1 Phase 3 Wire 120V 240V with neutral 96 138 166 276 3Y 208 N and ØA 3D 240 ØA and ØB 3 Phase 3 Wire Delta 208V no neutral n a 166 276 3D 240 ØA and ØB 3 Phase 3 Wire Delta 400V no neutral non N A n a 320 460 3D 400 ØA and ØB 3 Phase 3 Wire Delta 480V no neutral n a 384 552 3D 480 ØA and ØB 3 Phase 4 Wire Wye 120V 208V with ne...

Страница 5: ... CT ØA CT ØC CT L1 Neutral Earth 2 2 2 Single Phase Two Wire No Neutral This circuit occurs in residential commonly 120 240 Vac and some commercial applications The meter is powered from the ØA and ØB terminals We recommend connecting the N terminal to ground to provide a clean voltage reference for the measurement circuitry no current will flow through this terminal ØB ØC N ØA WATTNODE ØB CT ØA C...

Страница 6: ...phase delta service to be labeled as the C phase instead of the B phase The WattNode meter will work correctly with the high leg connected to ØA ØB or ØC See the web article https ctlsys com support four_wire_delta_circuits for more information ØB ØC N ØA WATTNODE ØB CT ØA CT ØC CT L3 L2 L1 Neutral Earth 2 2 7 Grounded Leg Service In rare cases with delta services or single phase two wire services...

Страница 7: ...ed in an electrical service panel or an enclosure Do not use the meter as a drilling guide the drill chuck can damage the screw terminals and metal shavings may fall into the connectors The meter has two mounting holes spaced 5 375 in 137 mm apart center to center These mounting holes are normally obscured by the detachable screw terminals Remove the screw terminals to mark the hole positions and ...

Страница 8: ...nts the WattNode Pulse meter may only be used with UL Listed CTs with a 333 mVac output or the following UL Recognized current transformer models which all generate 333 millivolts AC at rated current See the current transformer datasheets for CT ratings ACT 0750 xxx CTL 1250 xxx CTM 0360 xxx CTS 0750 xxx CTS 1250 xxx CTS 2000 xxxx CTB WxL xxxx CTT 0300 xxx CTT 0500 xxx CTT 0750 xxx CTT 1000 xxx CT...

Страница 9: ...ically isolated from dangerous voltages If the output wiring is near line voltage wiring use wires or cables with a 300 V or 600 V rating not less than the service voltage If the output wiring is near bare conductors it should be double insulated or jacketed You may install two wires into each screw terminal by twisting the wires together inserting them into terminal and securely tightening Note a...

Страница 10: ...n configuring the WattNode meter see the appropriate Operating and Reference Guide for your model The meter does not include a display or buttons so it is not possible to configure or monitor the meter directly other than the basic LED diagnostics described below 4 2 Power Status LEDs The three status LEDs on the front of the meter can help indicate correct measurements and op eration The A B and ...

Страница 11: ... Red Red Red C B A For other LED patterns see the Operating and Reference Guide or contact support for assis tance 4 3 Monitoring The WattNode Pulse models uses opto isolator outputs that simulate contact closures These are generally connected to a data logger or similar monitoring device which can count pulses to measure energy 4 4 Pulse Scale Factors See the Operating and Reference Guide for ful...

Страница 12: ...t can be performed by the user other than checking for errors via the status LEDs In the event of any failure the meter must be returned for service contact CCS for an RMA For a new installation follow the troubleshooting instructions in the Operating and Reference Guide before returning the meter for service to ensure that the problem is not connection related The WattNode meter should not normal...

Страница 13: ...m Surge 4kV according to EN 61000 4 5 6kV for WattNode Revenue models Power Consumption The following table shows maximum volt amperes the power supply ranges typical power consumption and typical power factors with all three phases powered at nominal line voltages The power supply consumes most of the total power while the measure ment circuitry draws 1 10 of the total 6 96 milliwatts per phase d...

Страница 14: ...t Voltage At CT Rated Current 0 33333 Vac RMS Absolute Maximum Input Voltage 5 0 Vac RMS Input Impedance at 50 60 Hz 23 kΩ 5 4 Pulse Outputs Full Scale Pulse Frequencies Standard All Models 4 00 Hz Custom Bidirectional 0 01 Hz to 600 Hz Custom Option P3 Option PV Option DPO 0 01 Hz to 150 Hz Absolute Maximum Pulse Output Frequencies Standard Models Bidirectional 900 Hz Option P3 Option PV Option D...

Страница 15: ... 2 5 mm2 300 V screw torque 4 4 lbf in 0 5 N m 5 8 FCC Information This equipment has been tested and complies with the limits for a Class B digital device pursuant to part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired o...

Страница 16: ...erations or repairs by anyone other than CCS Except as set forth herein CCS makes no warranties expressed or implied and CCS dis claims and negates all other warranties including without limitation implied warranties of merchantability and fitness for a particular purpose 5 10 Limitation of Liability In no event shall CCS be liable for any indirect special incidental punitive or consequen tial dam...

Отзывы: