Installation
—
CPSA-PCB100 Reference Manual
—
98
—
3.
Cable Connection
1.
Power
Power Cable
Use the power cable described below.
Cable
Twisted pair cable (when using a single wire, twist V+ wire and V- wire)
Applicable wire
AWG20 – 16(0.5mm
2
– 1.25mm
2
)
Cable Length
Within 3 meters
*Refer to
in the
page 79
for details of the power connector and pin assignment.
FG Cable
Use the FG cable described below.
Applicable wire
AWG18 – 16(0.75mm
2
– 1.25mm
2
)
Specification of External Power Supply
This product is designed to operate at least with 30 – 90 watt power supply.
In addition, the power supply must fulfill the following requirements.
Rising time for up
to 24V
2 milliseconds up to 30 milliseconds
Cable
Use copper wires that tolerate a temperature of 75 °C or higher.
Recommended power supply is the optional products of the CPS-PWD-30AW24-01 or CPS-PWD-
90AW24-01(CONTEC).
CAUTION
If the maximum output current of the external power supply is smaller than the maximum
consumption current of the product, the abnormal operations might occur due to the inrush
current at the start-up time or the load fluctuation. The aging external power supply could cause
a start-up failure
Содержание CONPROSYS Alpha Series
Страница 31: ...31 CONPROSYS WEB Setting This chapter describes the product system and functions...
Страница 47: ...47 PLC Backup This section describes PLC Backup menu and each of the setting procedure...
Страница 100: ...100 Troubleshooting This section describes how to solve the troubles when the product does not function properly...
Страница 109: ...Appendix CPSA PCB100 Reference Manual 109 2 Physical Dimensions mm 94 7 5 1 44 7 124 8 14 Open Lock 4 18...
Страница 119: ...119 Index...