Function
—
AI-1204Z-PE Reference Manual
—
55
—
Conversion data in-range comparison
The in-range compare start condition is established when the level on the specified analog channel
enters the range specified by level 1 and level 2. Saving of conversion data to memory is performed
for the sample points indicated by the black dots. If the analog signal already exist within the in-
range, the convention starts immediately.
Start condition : Level 2
≤
Analog signal
≤
Level 1
Conversion data out-of-range comparison
The out-of-range compare start condition is established when the level on the specified analog
channel is outside the range specified by level 1 and level 2. Saving of conversion data to memory
is performed for the sample points indicated by the black dots. If the analog signal already exist
within the out-range, the convention starts immediately.
Start condition : Analog signal
≤
Level 2 or Level 1
≤
Analog signal
External trigger
The product starts waiting for an external control signal as soon as the operation start command is
output.
Sampling and conversion data transfer to memory start when the specified edge (rising edge or
falling edge) is input from the external control signal.
Event controller output
This product starts waiting for an external control signal as soon as the operation start command is
output. Sampling and data transfer to memory start when the specified event controller output is
received.
Refer to the explanation of the event controller functions or to the driver help for details about the
event controller.
Содержание AI-1204Z-PE
Страница 4: ... 4 Table of Contents Customer Support and Inquiry 82 1 Services 83 ...
Страница 19: ... 19 Setup This section explains how to set up this product ...
Страница 33: ... 33 Installation This section describes how to connect to an external device with a cable ...
Страница 42: ... 42 Software This section describes analog input and output driver for Windows developed by CONTEC ...
Страница 47: ... 47 Function This section describes the features achieved by combining hardware and driver functions ...
Страница 72: ... 72 Appendix This section lists the specifications and the physical dimensions of the product ...
Страница 76: ... Appendix AI 1204Z PE Reference Manual 76 2 Physical Dimensions ...
Страница 77: ... Appendix AI 1204Z PE Reference Manual 77 3 Circuit Block Diagram ...