63
6.3
COMMISSIONING
/
Pour approx. 7 litres of water into the salt container.
/
Fill 25 kg of regeneration salt into the salt container.
The regeneration salt must comply with the requirements of DIN EN 973, or local equivalent, and be of
food-grade quality.
We recommend high-grade regeneration salt in tablet form (KBN: SALZT).
When using other
regeneration salts, clean the salt container (6) more often and replace the suction strainer in shorter
intervals.
/
Remove the cover.
/
Note down the installation date on the label (see fig. 8) and in the service record sheet (chapter 12).
/
Open the water supply (main water tap or shut-off valve).
/
Ensure that the bypass valve is set to “operation”.
1. Flushing the water softener:
/
Open a water tap (if possible, near the water softener) and adjust a volume flow of approx. 500 l/h.
/
After one minute of flushing (resin container is vented), insert the mains plug into the mains socket.
After connection to the mains, the control electronics will automatically perform a self-test.
Fig. 8: Device no., order no. and label “Installation date”
For safety reasons the water softener must be flushed and regenerated immedi-
ately for venting after the water supply is opened.
Order no.
Device no.
Label “Installation date”
Содержание CLEAR SOFT
Страница 39: ...39 10 6 2 ELEKTRONISCHE STEUERUNG Abb 17 Elektronische Steuerung mit St rmelderelais...
Страница 40: ...40 11 ERSATZTEILE Abb 18 Ersatzteile CLEAR SOFT A G D F B C E...
Страница 81: ...81 10 6 2 ELECTRONIC CONTROL Fig 17 Electronic control with fault indication relay...
Страница 82: ...82 11 SPARE PARTS Fig 18 Spare parts CLEAR SOFT A G D F B C E...
Страница 123: ...123 10 6 2 STEROWNIK ELEKTRONICZNY Rys 17 Sterownik elektroniczny z przeka nikiem do informacji o b dach...
Страница 124: ...124 11 CZ CI ZAMIENNE Rys 18 Cz ci zamienne CLEAR SOFT A G D F B C E...