40
Resetting a DIP switch
/
Remove the cover.
/
Unplug the power supply unit.
/
Reset the DIP switch. Ensure that only one contact is switched to the “ON” position.
/
Plug the power supply unit in.
/
Position the cover.
6.4
DISPLAY OF THE SET LIMIT VALUES
The set value of the DIP switch is indicated by the assigned LED of the LED row below.
6.5
AUTOMATIC OPERATION
Water consumption is constantly monitored. If during drawing of water one of these limits is exceeded, the
control sensor shut-off valve closes. The closed shut-off valve is indicated by the red “Closed” LED.
If the shut-off valve is closed after exceeding of the “Max. water volume” limit or “Max drawing time”, then
the control sensor opens its shut-off valve after 30 s to perform a water flow check:
Setting examples
S1
max. water flow
[m³/h]
S2
max. water volume
[m³]
S3
max. drawing time
[h]
Single family dwelling,
2 persons,
no pressure flushing valves
2
0.2
0.5
Single family dwelling,
4 persons,
no pressure flushing valves
2
0.5
1
Single family dwelling,
4 persons,
2 pressure flushing valves
5
0.5
1
If a water softening system is fitted, then the max. drawing time must be set to at
least the regeneration time.
If for example with the DIP switch S1 “m³/h“, contact 3 is switched to “ON”, then
in the corresponding LED row, the third LED illuminates. On the transparent
screen, this LED is labelled with the value 2. In this case the max. flow then equals
2 m³/h. This corresponds to a fully open ¾" tap with average water pressure.
Содержание CLEAR 2.0 SAFE
Страница 12: ...12 6 BETRIEB Abb 5 CLEAR 2 0 SAFE mit abgenommener Abdeckhaube Abb 6 CLEAR 2 0 SAFE Schaltung...
Страница 36: ...36 6 OPERATION Fig 5 CLEAR 2 0 SAFE with removed cover Fig 6 CLEAR 2 0 SAFE switch...
Страница 60: ...60 6 EKSPLOATACJA Rys 5 CLEAR 2 0 SAFE ze zdj t os on Rys 6 CLEAR 2 0 SAFE uk ad elektryczny...
Страница 74: ...74 Notizen Notes Notatki...
Страница 75: ...75 Notizen Notes Notatki...