Operating Instructions
Single-pole Conductor Rail System
SingleFlexLine Program 0815
BAL0815-0002g-US
www.conductix.us
translated document
page 49 of 128
Fig. 41: Standard hanger clamps for screwing on
Use the QR code (“click” or “scan”), to watch our animation
Mounting Hanger Clamps (clip-in, screwable and turnable).
6.3.3.2
Mounting the fixed point
A fixed point consists of a hanger clamp and 2 fixed point clamps per pole. The positions of the fixed points are determined when
planning the system. The correct positioning of the fixed points is crucial for the thermal expansion behavior of the conductor rail
system.
Establishing a fixed point:
→
Install a fixed point to the left and right of a hanger clamp per conductor rail pole. The fixed point cap is secured by an insertion
cam in a hole in the side wall of the conductor rail.
→
Scribe the position on the conductor rail before installation.
→
Place the fixed point cap on the conductor rail as a drilling jig and drill a 3-mm hole through the insulation and copper profile on
one side.
→
Remove the fixed point cap and replace it after rotating through 180° and insert an insertion cam into the hole.