10.2
Fault correction table
Fault
Cause
Corrective Measures
Sliding contacts are
unevenly worn.
Range of movement of the current collector head is
restricted
Use original current collector
heads from Conductix-Wampfler
(ensure freedom of movement).
Mount current collector according
to Section 6.4.4 . Check the
installation position at various
points in the system.
Contact pressure is too high or low.
Mount current collector according
to Section 6.4.4; Use original
connecting cables from
Conductix-Wampfler (use
superfine-stranded Class 6
connecting cables (in accordance
with IEC 60228)).
Sliding contact insulation is
abraded on the side down to
the sliding contacts.
For horizontal installation: The height of the current
collectors is not set correctly.
Replace current collector heads;
correctly adjust the height of the
current collector.
Sliding contacts wear out
too fast.
Sharp edges on the power terminal, conductor rails,
connections between the conductor rails.
Smooth out sharp edges with a
file, compressed-air grinder or
sanding paper.
Conductor rails soiled or scorched in places.
Check current values; clean rails
as specified in Maintenance
Instruction WV0800-0002; if
necessary, replace conductor
rails.
Contact pressure too high.
Mount current collector according
to Section 6.4.4. Check the
installation position at various
points in the system.
The power supply is not
continuous, contact is
disrupted.
Line feed connector and feed terminal not properly
connected.
Tighten all screws to the specified
torque, see 6.4.2; If necessary,
recrimp and reinstall the crimping
cable lug.
Current collector not properly connected.
Install current collector as
specified in Section 6.4.4; correct
connecting cable, replace if
necessary
Contact pressure too low.
Only use original Conductix-
Wampfler current collectors,
check cable position (ensure that
cables can move freely). Install
current collector as specified in
Section 6.4.4; correct connecting
cable, replace if necessary.