background image

Operating Instructions 
 
Insulated Conductor Rail System 

SinglePowerLine Program 0813 

 

 

BAL0813-0007-EN 
www.conductix.com 

translated document 

page 100 of 108 

10.2

 

Fault correction table 

Fault 

Cause 

Corrective Measures 

Sliding contacts are 
unevenly worn. 

Range  of  movement  of  the  current  collector  head  is 
restricted 

Use original current collector 
heads from Conductix-Wampfler 

(ensure freedom of movement). 
Mount current collector according 

to Section 6.4.4 . Check the 
installation position at various 
points in the system. 

Contact pressure is too high or low. 

Mount current collector according 
to Section 6.4.4; Use original 
connecting cables from 

Conductix-Wampfler (use 
superfine-stranded Class 6 
connecting cables (in accordance 

with IEC 60228)). 

Sliding contact insulation is 
abraded on the side down to 
the sliding contacts. 

For  horizontal  installation:  The  height  of  the  current 
collectors is not set correctly. 

Replace current collector heads; 
correctly adjust the height of the 
current collector. 

Sliding contacts wear out 
too fast. 

Sharp  edges  on  the  power  terminal,  conductor  rails, 
connections between the conductor rails. 

Smooth out sharp edges with a 
file, compressed-air grinder or 
sanding paper. 

Conductor rails soiled or scorched in places. 

Check current values; clean rails 
as specified in Maintenance 
Instruction WV0800-0002; if 

necessary, replace conductor 
rails. 

Contact pressure too high. 

Mount current collector according 
to Section 6.4.4. Check the 

installation position at various 
points in the system. 

The power supply is not 
continuous, contact is 

disrupted. 

Line  feed  connector  and  feed  terminal  not  properly 
connected. 

Tighten all screws to the specified 
torque, see 6.4.2; If necessary, 
recrimp and reinstall the crimping 

cable lug. 

Current collector not properly connected. 

Install current collector as 

specified in Section 6.4.4; correct 
connecting cable, replace if 
necessary 

Contact pressure too low. 

Only use original Conductix-
Wampfler current collectors, 

check cable position (ensure that 
cables can move freely). Install 
current collector as specified in 

Section 6.4.4; correct connecting 
cable, replace if necessary. 

Содержание 0813 Series

Страница 1: ...Operating Instructions Insulated Conductor Rail System SinglePowerLine Program 0813 BAL0813 0007 EN www conductix com translated document page 1 of 108 Order Number 0813xx...

Страница 2: ...ctive equipment 9 2 4 Intended use 10 2 5 Unintended use 11 2 6 Protective measures by the operator user 12 2 7 5 Safety Rules for working on electrical systems 12 2 8 Special hazards 13 2 8 1 Electri...

Страница 3: ...ductor rail system 49 6 4 3 1 50 6 4 3 2 Mount hanger clamps 50 6 4 3 3 Mount conductor rail 54 6 4 3 4 Connect rails 57 6 4 3 5 Line feed 60 6 4 3 6 Mount anchor clamp 63 6 4 3 7 Mount heating wire o...

Страница 4: ...Stopping the system 90 8 4 Continue operation 91 9 Maintenance and Service 92 9 1 Safety 92 9 2 Tools and materials 95 9 3 Maintenance plan 96 10 Troubleshooting 97 10 1 Safety 97 10 2 Fault correcti...

Страница 5: ...ddition to these operating instructions the instructions located in the appendices for the individual assembled components also apply 1 2 Limitation of liability All data and information in these oper...

Страница 6: ...laims remains unaffected 1 4 Replacement parts WARNING Incorrect replacement parts are a safety hazard Incorrect or faulty replacement parts can impair safety and result in damage malfunctions or comp...

Страница 7: ...s situation which if not avoided may result in death or serious injury DANGER indicates an immediately hazardous situation due to electricity which if not avoided may result in death or serious injury...

Страница 8: ...engineers or electrical technicians Personnel are also considered qualified who have been employed correspondingly for several years have been educated in theory and practice during that time and who...

Страница 9: ...ing for better traceability Example of instruction log Date Name Type of Training Training given by Signature 11 05 2009 John Doe First safety training for personnel Horst M ller 2 3 Personal protecti...

Страница 10: ...ction 2 5 Claims of any kind due to damages from unintended use are excluded The operator bears sole liability for all damage that results from unintended use Intended use The SinglePowerLine 0813 Con...

Страница 11: ...ended use are excluded The operator bears sole liability for all damage that results from unintended use Unintended use particularly includes the following forms of use Operation in unsuitable environ...

Страница 12: ...s The operator must provide personnel with all required protective equipment work clothes safety shoes hearing protection protective gloves safety helmet goggles breathing mask The operator must keep...

Страница 13: ...s and connections within switching cabinets control systems etc Parts that have come under voltage due to a fault Before working on the parts listed above Disconnect the conductor rail system from the...

Страница 14: ...ar conductor rails Check service and clean conductor rails regularly and as prescribed See Section 8 and 9 2 8 2 Mechanical hazards and sources of danger DANGER Risk of injury due to ensnarement or im...

Страница 15: ...cked plants take effective measures to protect employees from the dust During all work on the conductor rail system in which collected dust can be stirred up wear personal protective equipment In part...

Страница 16: ...ts For example hanger clamps can break and the conductor rail system can fall down Check the influencing factors of temperature exposure time concentration and interactions Use in chemical works galva...

Страница 17: ...lfunctions Measures in the event of accidents Shut down the system and secure it against unauthorized unintentional and or erroneous reactivation Secure the danger zone Remove persons from the danger...

Страница 18: ...um conductor temperature 85 C 115 C for heat resistant version PPE SB briefly 125 C Protection type With current collector insertion from below IP23 DIN EN 60529 VDE 0470 1 with current collector inse...

Страница 19: ...stainless steel sliding surface CopperECO Copper Information regarding resistances are general notes and depend on the temperature exposure time concentration and interactions and must be verified in...

Страница 20: ...ased heating if the current collector is operated outside the permissible installation position 3 2 Tolerances The conductor rail must be installed within the following tolerances Conductix Wampfler d...

Страница 21: ...or explosive gases or dusts In flammable or explosive materials in the vicinity particularly below the conductor rail In dusty environments Outdoors with free weathering In environments with relative...

Страница 22: ...ent collector The current collector head of the current collector is pressed against the conductor rail with a continuous contact pressure The electrical energy is transferred to the current collector...

Страница 23: ...translated document page 23 of 108 Fig 2 System overview 0813 Pos Name 1 End cap 2 Support arm 3 Hanger clamp 4 Anchor clamps 5 Connector 6 Line feed connector 7 Towing arm 8 Single current collector...

Страница 24: ...ated document page 24 of 108 The rails are straight or curved A distinction is made between horizontal and vertical rail arrangements Fig 5 Horizontal bend inner and outer bend horizontal arrangement...

Страница 25: ...crews Electrical interfaces The current collector head is connected to the electrical system of the mobile consumer via a flexible connecting cable The connecting cable can be supplied in the scope of...

Страница 26: ...bracket bracket The conductor rails are fastened to a straight smooth surface provided by the customer using hanger clamps The conductor rails are electrically and mechanically coupled using connector...

Страница 27: ...e Fig 11 Hanger clamp 0813 without insulator hexagon Hanger clamp 08134 Hanger clamps for supporting the conductor rail The hanger clamps are designed for mounting on a support arm or C rail The hange...

Страница 28: ...compact screw connectors Depending on the conductor material of the conductor bar the connectors have either a stopper aluminum with stainless steel strip and CopperECO or an inspection window copper...

Страница 29: ...ing caps Line feed connector 081351 The line feed takes place via line feed connectors These are used instead of normal connectors The electrical connection is made via spacer bolts and tubular cable...

Страница 30: ...expanded from this point The fixed point is typically attached near the line feed If several fixed points are projected for example with transfers or curves natural fixed point the route between the f...

Страница 31: ...odate a maximum 45 mm expansion The expansion units are delivered pre assembled on a conductor rail 5000 mm The middle section of the expansion unit must be supported with a hanger clamp not included...

Страница 32: ...allation dimension between towing arm and sliding surface 125 mm Fig 27 Double current collector Double current collector 08130 Contact pressure 2 x 28 N Lateral deflection 100 mm Working stroke in in...

Страница 33: ...pport arm Sendzimir hot dip galvanized steel Fig 29 Bracket for screwing on with 2 hole connection plate steel galvanized Fig 30 Support arm bracket Bracket steel blank Small parts steel galvanized Su...

Страница 34: ...ckets anti twist clamping thickness 6 25 mm galvanized steel Clamping brackets 020180 020181 08 Clamping brackets can also be used for example to attach a support arm to the customer s support structu...

Страница 35: ...ons with high pollution and outdoor applications up to 1000 V rated voltage They are only used when the current collector is inserted from below Fig 36 Towing arm for current collector steel galvanize...

Страница 36: ...requirements of the VDE regulations a hole must be drilled in the towing arm of systems with pickup guides with the drilling jig which is used to accommodate the bolt on the protective conductor curr...

Страница 37: ...ix com translated document page 37 of 108 Fig 40 Tool 1 Fig 41 Tool 2 Disassembly tool 0813 08 V015 0493 The disassembly tool consists of two tools and is an aid for removing a hanger clamp from the c...

Страница 38: ...ones Do not attach ropes or straps at sharp corners and edges and do not knot or twist them Only move loads under supervision Set down the load before leaving the workplace Cordon off the work area Us...

Страница 39: ...use the attachment points provided Only remove packaging shortly before installation 5 2 Transport Immediately upon receipt check the delivery for completeness and transport damage In case of visible...

Страница 40: ...age a specialist to handle disposal 5 4 Storage of packaged parts Store packaged parts under the following conditions Do not store outdoors Store in a dry dust free place Do not expose to aggressive m...

Страница 41: ...ury due to improper installation Improper installation can result in serious injury to persons and property Before starting work ensure that there is sufficient space for the installation Handle open...

Страница 42: ...e equipment DANGER Risk of injury due to ensnarement or impact An ensnarement and or impact with moving conductor rails slip ring or current collectors connected to the machine and other components mu...

Страница 43: ...ock The main power supply from the building must be disconnected in the installation area and secured against switching on again Disconnect all voltage supply to the line feeds Check whether a voltage...

Страница 44: ...due to an electrical shock as well as by falling or being thrown across the room The system operator must ensure that the current collector does not protrude or must ensure that the danger area is in...

Страница 45: ...ing illustration provides an overview of the arrangement of the components and distances in a conductor rail system Conductor Rail System 0813 with hanger clamps on support arms Fig 42 Components in a...

Страница 46: ...Drilling jig for systems with guides Order No 08 W100 0223 Contact grease conductive paste Order No 080021 Personnel Installation only by technical personnel at least 2 persons 6 4 2 Trim conductor r...

Страница 47: ...ainless steel strip will loosen in the conductor bar Always adhere to the cutting direction Fig 44 Note the sawing direction for the conductor bar Saw the insulating profile accordingly It must always...

Страница 48: ...file NOTE Sharp edges and or burrs can will lead to increased wear of the sliding contacts or even to the failure of the system A sharp edge and or burr can quickly wear away the sliding contacts Use...

Страница 49: ...e layout and allocation plan on the substructure Prepare the line feed and guide if present Install the conductor rail see Section 6 4 3 1 Install conductor rail sections Check the mechanical installa...

Страница 50: ...astening and or increased requirements e g vibration the fastening must be adapted to the respective application e g by means of additional screw locking with Loctite 242 The system manufacturer is re...

Страница 51: ...e project specific documents Distance between hanger clamps Hanger clamp to end cap 250 mm up to max 400 mm Hanger clamp to hanger clamp 2500 mm Work steps mounting with support arm C rail Slide the f...

Страница 52: ...see Fig 54 The phase offset of either 80 mm standard or 70 mm reduced can be set with the mounting comb Depending on which phase offset is to be implemented the corresponding side 4x80 mm or 4x70 mm...

Страница 53: ...e screw connection from the hanger clamp Insert the hanger clamp into the hole in the retaining plate and tighten the screw connections from above with an open end wrench SW 17 14 Nm see Fig 57 throug...

Страница 54: ...nalysis The operator must take appropriate measures Requirements The hanger clamps are correctly mounted on the support structure Work steps Mount the conductor rails according to the project specific...

Страница 55: ...ductor rail and hanger clamp see Fig 62 Press the conductor rail against Tool 1 or against the hanger clamp see Fig 63 At the same time insert Tool 2 on the open side of the conductor rail see Fig 65...

Страница 56: ...3 BAL0813 0007 EN www conductix com translated document page 56 of 108 Fig 66 The hanger clamp bends up Fig 67 Remove Tool 2 from the open side of the conductor rail In order to remove Tool 1 the tens...

Страница 57: ...3 6 Anchor clamps are positioned to the right and left of a hanger clamp Please refer to the project specific documents for the exact position of the anchor clamps NOTE Aluminum stainless steel and Co...

Страница 58: ...n the function a gap of 2 to max 3 mm between the rail ends is functionally necessary The clamping plate Pos 7 see Fig 78 must lie in the hollow profile of the conductor bar NOTE In the case of alumin...

Страница 59: ...ide the insulating cap halves of the connector over the connection point see Fig 76 and tighten the two fillister head tapping screws Pos 6 see Fig 77 Fig 76 Slide the insulating cap halves of the con...

Страница 60: ...as possible to the feed cable of the permanent installation see Section 6 4 3 4 If the line feed is provided within a section of rail that has been cut to length the insulating profile must be separa...

Страница 61: ...beforehand and connecting it to the sleeve with a hot air blower after installation Fig 81 Slide the cable ends through the sleeves To ensure a good current transfer over the long term the conductor...

Страница 62: ...ug Crimp the stripped end of the connecting cable Pos 2 with the tubular cable lug Pos 5 Fig 83 Crimp cable end Pos 2 with tubular cable lug Slide the two insulating cap halves Pos 1 together and scre...

Страница 63: ...animation Connecting Rails and Mounting Line Feed 6 4 3 6 Mount anchor clamp The conductor rail is fixed at one point by means of anchor clamps and can expand freely from this point The fixed point is...

Страница 64: ...ls Open end wrench SW8 Work steps Slide the anchor clamps onto the clipped in conductor rail section on the right and left see Fig 87 When sliding on the anchor clamps ensure that the two side screws...

Страница 65: ...ing loss of contact with the current collector The conductor rail is heated using an electrical heating conductor that is fed into the insulation profile It lies in the hollow cavity of the insulation...

Страница 66: ...from the power supply The heating can be designed as a separate electrical circuit and may need to be disconnected from the power separately from the conductor rail Disconnect the power supply of each...

Страница 67: ...luded in the scope of delivery on the customer s support structure substructure The use of a double current collector is recommended when using expansion units Required tools Open end wrench SW17 Work...

Страница 68: ...ion of the two lines and read off the air gap to be installed Example Temperature range From 5 C to 45 C Ambient temperature during installation 23 C Air gap 20 mm per expansion point 2 x 20 mm for th...

Страница 69: ...current collector Requirements The ends of the conductor rail ends are deburred see Fig 46 and not connected with a connector Please refer to the project specific documents for the exact position of a...

Страница 70: ...with fastening elements consisting of hexagon screw DIN931 M6x50 Pos 5 8 Nm and lock nut DIN985 Pos 6 mounted on the end caps see Fig 93 Slide the hanger clamp onto the anchor clamp Fig 93 Mount the...

Страница 71: ...o the screw on the side of the anchor clamp Place the bridging plate Pos 9 over the bolt of the hanger clamp and screw together with the DIN 934 nut Pos 13 14 Nm Mount the cover Pos 14 onto the hanger...

Страница 72: ...d potential constructive differences Use the QR code click or scan to see our animation Mounting the Air Gap Insulation Section 6 4 3 10 Mount end caps Required tools Hexagon screwdriver SW5 Rubber ma...

Страница 73: ...d Conductor Rail System SinglePowerLine Program 0813 BAL0813 0007 EN www conductix com translated document page 73 of 108 Fig 98 End cap on the conductor rail end Fig 99 The end cap is mounted correct...

Страница 74: ...Tighten the cylinder screw DIN912 M6x35 Pos 3 see Fig 100 Fig 100 Tighten cylinder screw Insert the lamellar plugs Pos 4 into the hole see Fig 101 Fig 101 Insert the lamellar plugs over the cylinder s...

Страница 75: ...the x and y directions are not permitted The pickup guide centers the current collector with a maximum lateral and vertical offset of 25 mm settings of less than 10 mm are recommended NOTE For systems...

Страница 76: ...Program 0813 BAL0813 0007 EN www conductix com translated document page 76 of 108 Fig 104 Important dimensions for systems with pickup guides NOTE Please also note the information on installing the P...

Страница 77: ...lamps in front of the pickup guide was reduced from 80 mm to 65 mm Distances Pickup guide to the first hanger clamp 560 mm Required tools Rubber mallet Hexagon screwdriver SW5 Work steps The pickup gu...

Страница 78: ...the single current collector 250 A Single current collector 250 A Maximum current load 250A Max travel speed 600 m min higher travel speeds on request Contact pressure 28 N Lateral deflection 100 mm...

Страница 79: ...ted Conductor Rail System SinglePowerLine Program 0813 BAL0813 0007 EN www conductix com translated document page 79 of 108 Fig 108 Mount the central axis of the current collector exactly on the centr...

Страница 80: ...e moving range of the current collector and connecting cables Choose foreign objects such as fastening screws in such a manner that the movement of cables and current collectors is not affected In sys...

Страница 81: ...is Observe the current collector tolerances mounting dimensions check at the narrowest point in the case of curves The towing arm must not have any play or bend Required tools Open end wrench SW17 Wor...

Страница 82: ...er Pos D is seated on the bottom 6 4 4 2 Typical mounting errors Rail joints and transfers have not been deburred Distance within connectors was not maintained on end with Alu CopperECO from 2 to max...

Страница 83: ...113 Only use only highly flexible Conductix Wampfler cables In principle connecting cables with copper wires are to be used Use ferrules with insulation collars for the flexible connecting cables For...

Страница 84: ...and legal regulations Always ensure that all the installation work has been fully completed before each commissioning Always ensure that all components have been properly installed before each commiss...

Страница 85: ...danger zone in particular if protective devices covers enclosures control devices etc have been removed or deactivated Use caution when working in the vicinity of the danger zone particularly below t...

Страница 86: ...plate been affixed in a suitable location by the manufacturer The phase offset is 80 mm or 70 mm see Section 6 4 3 1 Has the phase offset of the 2 3 hanger clamps in front of a pickup guide if present...

Страница 87: ...conductor bars conductor rails and slip rings 50 k EN 60204 1 18 3 2018 For systems with heating Test Tested Has the heating wire if present been connected according to the project specific documents...

Страница 88: ...ter initial commissioning Current collector undamaged and without signs of heavy wear Conductor rail components undamaged and in the proper location No displacements or distortions Check hanger clamps...

Страница 89: ...and contacts a conductive material Take the following measures Ensure proper electrical protection at all times Ensure grounding of metallic components at all times Ensuring the function of the custo...

Страница 90: ...y with the required tolerances Take the following measures Conduct electrical testing as prescribed before commissioning Permissible current values must be observed Maintain tolerances during operatio...

Страница 91: ...s in the conductor rails Perform a visual inspection The insulation resistance corresponds to the locally applicable technical directives As needed before the device or system is started measure the i...

Страница 92: ...voltage supply Check whether a voltage is still present in the components and take measures where necessary The customer must provide grounding for metallic components The customer must provide protec...

Страница 93: ...bars and plastic There is a health hazard due to airborne respirable dust Sensitization may occur if handling the conductor rail frequently and or carelessly handling dust accumulation Cancer mucous...

Страница 94: ...hazard due to overload or sparking A fire hazard can occur due to overloads of the cable electrical arcing or short circuits Before recommissioning ensure that all work has been completed and all comp...

Страница 95: ...this task See Section 12 1 Replacing conductor rails DANGER Risk of injury due to cutting and amputation The ends of the conductor bars can have sharp edges particularly if they were cut to size on si...

Страница 96: ...he required maintenance intervals should be shortened according to the actual signs of wear Contact the manufacturer in case of any questions regarding maintenance tasks and intervals see the service...

Страница 97: ...r rail system according to the 5 Safety Rules and secure it against switching on again For the 5 Safety Rules see Section 2 5 DANGER Risk of death due to electrical shock Contact with components carry...

Страница 98: ...ipment Protective eyewear Dust mask Class FFP3 observe local regulations Protective gloves Disposable coveralls Prevent contamination of the environment e g people goods production facilities etc whil...

Страница 99: ...ards directives and legal regulations Conduct locally required electrical tests WARNING Danger of injury due to hot surfaces Components can get hot during operation Wear personal protective equipment...

Страница 100: ...height of the current collector Sliding contacts wear out too fast Sharp edges on the power terminal conductor rails connections between the conductor rails Smooth out sharp edges with a file compres...

Страница 101: ...e damaged components Abrasive dust has collected at one of the more frequently used transfer points where the direction of travel is reversed Adjust the consumer s movement profile Move over the end p...

Страница 102: ...ue to electrical shock Contact with components carrying electrical power can lead to death or severe injury due to electrical shock Danger of injury due to shock reactions falling or being thrown acro...

Страница 103: ...hazards Disassemble components properly Be aware of the dead weights of the components If necessary use lifting gear Secure components so they cannot fall or topple DANGER Risk of injury due to cuttin...

Страница 104: ...oduction facilities etc while cleaning by taking appropriate measures use covers barriers filter systems Do not blow out dust with compressed air but rather vacuum it away The vacuum must be equipped...

Страница 105: ...ired tools Disassembly tool Order No 08 V015 0493 see work steps on P 55 Hexagon screwdriver SW 5 Open end wrench SW 17 Screwdriver set Cutting tool e g jigsaw angle grinder Tools for securing 11 3 Di...

Страница 106: ...documents ID No Document Number Document Name 01 WV0800 0001 Cleaning of Conductor Rails 02 WV0800 0002 Maintenance Schedule Conductor Rails 03 MV0800 0018 Insulation measurement of heating wires 04...

Страница 107: ...Operating Instructions Insulated Conductor Rail System SinglePowerLine Program 0813 BAL0813 0007 EN www conductix com translated document page 107 of 108 12 2 Air gap diagram...

Страница 108: ...bility 5 Maintenance and Service 92 Malfunctions 17 Material defects 6 Operation 89 Operator 12 Packaging 39 Personnel requirements 8 Product Description 22 Protection against contact 44 Protective me...

Отзывы: