Figure 5:
DIP switch location (cover removed)
Before operating the DIP switch, ensure the humidifier power source’s leakage current circuit breaker is
turned to the OFF position, and power supply has been completely stopped. Changing any DIP switch
pin while power is still being supplied to the unit may result in settings not being properly implemented.
LED lights on the control unit indicate the status of the humidifier, including faults. Refer to the table
below for their definitions.
Table 3: LED pattern
LED No.
(Colour)
LED Illumination Pattern
LED 1 (green)
Blinks slowly (0.5-second intervals) when communicating with remote controller, and blinks quickly
(0.1-second intervals) when a communication error has occurred.
LED 2 (yellow)
Blinks or solidly illuminates in accordance with water supply unit operation count: 0.5-interval blinking to
indicate 500,000 times or more, 0.1-second interval blinking to indicate 950,000 times or more, and solid
illumination to indicate 1 million times (approx. 5 years, at 5000 annual hours of operation per year).
LED 3 (red)
Illuminates to indicate detection of high water level in drain pan (press reset button BS1 to cancel illumina
-
tion).
LED 4 (green)
Illuminates to indicate detection of water leakage (press reset button BS1 to cancel illumination).
LED 5 (yellow)
Illuminates to indicate detection of water supply solenoid valve leakage or drain error in waste water drain
-
age pump (press reset switch BS1 to cancel illumination).
LED 6 (red)
Reserved.
LED 7 (green)
Illuminates to indicate detection of drain error in drain pump (press reset button BS1 to cancel illumina
-
tion).
LED 10 (green) Illuminates when drain pump is in operation.
Board power switch
Control unit cover
Screws
default: All pins set to OFF