31
Installation
5.5.3 Installation work external connections
5.5.3.1 Connection of the maximum humidistat "B1" and the optional air flow monitor
"B2" to the external safety loop
24V
HUM
GND
X4
X5
X3
X2
SC
SC
24V
LIM
GND
GND
24V
EXT
GT
RF
GF
B1
B2
11 11 14
1 2
L+ N–
NC C NO
0V 24V DO1 DO1
1 2 3 4
brown
green
green
white
yellow
white
Condair RH
Driver board
yellow
brown
The maximum humidistat "B1" and the optional Air flow monitor B2 "are connected to the corresponding
terminals of the terminal blocks" X3 "," X4" and" X5" on the driver board of the Condair RH according
to the diagram.
Note
: If no air flow monitor is connected, the yellow wire of the maximum humidistat "B1" is connected
directly to the "SC" terminal of terminal block "X3".
Note
: The wiring diagram shows the connection of the maximum humidistat "CHD-S"and the air flow
monitor "CAD-S", which are available as accessories. If other devices are used, these must be con-
nected respectively according to the instructions of the respective manufacturer.