Mounting the nebulizers
5.3
Mounting DRAABE TurboFogNeo 8
5.3.1 Additional information on positioning DRAABE TurboFogNeo 8
– The maximum installation height should not be exceeded so as to not make access unnecessarily
difficult.
– The air space in front should be free at a 360° angle and a distance of 4 m. (For further details, see
the graphic below)
– The stubs with the DN4 high-pressure hose, starting from the short T-connector, must not exceed
6 m in length.
5.3.2 Positioning DRAABE TurboFogNeo 8
A
1
2
3
B
C
(3 – 4 m)
D
(2 m)
C
(3 – 4 m)
D
(2 m)
C
A – Ceiling distance
B – Ground clearance
C – Free air gap to the front
D – Free air gap auxiliary line
1 – Object (e.g. pillars) in the permitted corridor
2 – Permitted corridor
3 – Aerosol mist
Fig. 9: Positioning DRAABE TurboFogNeo 8
Minimum clearances
TurboFogNeo8
Ceiling clearance [A]
1.0 m
Floor clearance [B]
4.0 – 6.0 m
Free air gap [C]
3.0 – 4.0 m
Free air gap [D]
2.0 m