46
Operating the Condair DL control software
5.3.5.6 Settings in the "Remote Fault Indica ..." submenu
09/01/2021
DL
07:00 pm
Indication
Safety Loop
Ag-Ion Exchange
Service
Warning
Error
Remote Fault Indica...
–
Indication
: With this setting you determine whether maintenance mes-
sages ("Service") only or all Warning messages ("Warning") are outputted
via the service relay of the remote operating and fault indication board.
Factory setting:
Service
Options:
Service
or
Warning
–
Safety Loop
: With this setting you determine whether an Error ("On") or
a Warning ("Off") is triggered when the external safety loop is open.
Factory setting:
Warning
Options:
Warning
or
Error
–
Ag-Ion Exchange
: With this setting you determine whether an Error ("On")
or a Warning ("Off") is triggered when the capacity counter of the silver
ionization cartridge has elapsed.
Note: However, 7 days after the capacity counter of the silver ionization
cartridge has elapsed always an error message is triggered.
Factory setting:
Error
Options:
Error
or
Warning