4.1.3.11.6 Setting the damping time for the limit signal in seconds
Note: This setting is available only if the modulation mode is set to “Dual” (see chapter 4.1..).
Select “
Lim-Damp
” in the internal control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue set the desired damping time for the limit signal in seconds
to eliminate regulation peaks.
Factory setting:
5 s
Setting range:
1 ... 20 s
4.1.3.11.7 Switching on and off the humidity alert function
Select “
RH Alerts
” in the internal control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue you can switch on or off the humidity alert function.
Factory setting:
On
Options:
On, Off
4.1.3.11.8 Setting the upper humidity alarm value
Note: This setting is available only if the humidity alert function is activated (see chapter 4.1..11.7).
Select “
RH High
” in the internal control settings menu, then press the
<Set>
key.
In the upcoming modification dialogue set the desired upper humidity alarm value for tirggering a
humidity alert.
Factory setting:
75 %rH
Options:
20 ... 95 %rH
Esc
Set
Limit Damping
5 s
5 s
Internal Settings
Limit-Band :15
Lim-Damp :5
RH Alerts :On
Lim.Setpoint:80
RH High :75
RH Low :33
Esc
Set
Controls
Controlsign.:0-10V
Limitsignal :0-10V
Short CD :Off
Unit Type :Set
Time Prop. :Off
Int.Settings:Set
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Esc
Set
RH Alerts
Off
On
On
Internal Settings
Limit-Band :15
Lim-Damp :5
RH Alerts :On
Lim.Setpoint:80
RH High :75
RH Low :3
Esc
Set
Controls
Controlsign.:0-10V
Limitsignal :0-10V
Short CD :Off
Unit Type :Set
Time Prop. :Off
Int.Settings:Set
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Internal Settings
Limit-Band :15
Lim-Damp :5
RH Alerts :On
Lim.Setpoint:80
RH High :75
RH Low :33
Esc
Set
Controls
Controlsign.:0-10V
Limitsignal :0-10V
Short CD :Off
Unit Type :Set
Time Prop. :Off
Int.Settings:Set
Esc
Set
Settings
Controls :Set
Power Limit :100
Water Mngm. :Set
Language :English
Remote Test :Set
Date :01.10.08
Esc
Set
Esc
Set
RH High
75 %rH
75 %rH