The CDD6 door drive can be configured by a parameters set, most of them are accessible also from the
door drive front panel. The following table reports all the parameters that can be changed by the door drive
front panel. The associated functions are described in detail in the next paragraphs.
The parameters
highlighted in the table represents the key parameters for the door operator configuration
.
N°
RANGE
UNIT
DEFAULT
Name
Values Description
00
[0 ; 1]
-
0
Reversing events management
00 = internal
01 = external when moving
01
[0 ; 2]
-
0
MLC commands check
00 or 01 = level.
02 = activation edge
02
[0 ; 2]
-
0
Door drive reaction on MLC
commands not present
00 = instant stop
01 = low speed + stop
02 = low speed cycle
04
[0 ; 2]
-
0
RVC input option
00 = reversing on RVC edge
01 = reversing on RVC active level
02 = mechanical safety edge
05
[0 ; 1]
-
1
Car door locking device
00 = car door lock not present
01 = car door lock present
06
[0 ; 1]
-
0
Glazed door
00 = not present
01 = present
07
[0 ; 3]
-
3
AUXS output options
00 = disabled
01 = active during door opening
02 = active after space % reached
03 = Alarm signal
08
[0 ; 99]
%
50
Space percentage
(related to P-07=2)
00 = door closed … 99 = door opened
0A
[0 ;2 ]
-
0
WiFi module enable
00 = disabled
01 = enabled
02 = reset Password & SSID
19
[0 ; 1]
-
1
Fire-Fighting mode
00 = stop without command
01 = EN81-72
20
[1 ; 5]
‘
1
Battery opening cycle duration
(related to EOC command function)
Expressed in minutes
21
[0 ; 2]
-
1
RVC signal logic
00 = OFF
01 = N.O.
02 = N.C.
31
[0 ; 2]
-
1
DETC signal logic
00 = OFF
01 = N.O.
02 = N.C.
22
[0 ; 1]
-
0
Closing rotation
00 = clockwise
01 = counter-clockwise
23
[10 ; 99]
%
70
% partial opening on AUXC active
when P-32=01
(00 = door closed)… 99 = door opened
28
[0 ; 15]
cm
9
Installed skate space in cm
On the front panel display the value
is shown in cm.
29
[0 ; 1]
-
0
PIN21 output option
00 = DISABLED
01 = BUZZER output