background image

Compool

Cp3800 POOL-SPA CONTROL SYSTEM

Installation & Operating Instructions

11/07/97
941-1064

Содержание Cp3800

Страница 1: ...Compool Cp3800 POOL SPA CONTROL SYSTEM Installation Operating Instructions 11 07 97 941 1064...

Страница 2: ......

Страница 3: ...Circuit Board 12 Low Voltage Cables 13 Valve Actuators 13 Gas Heater Connections 14 Water Temperature Sensor 14 Freeze Temperature Sensor 15 Control Panel 16 Modular Crimping Tool 17 System Options 1...

Страница 4: ...Programming 29 Programming additional Run Times 29 Programming a Time out 29 Programming a Once only 30 Canceling Programs 30 Setting the Time of Day 30 Remote Control at Spa key 30 Calibration 31 Po...

Страница 5: ...unless they are closely supervised at all times Water in excess of 100 degrees Fahrenheit may be hazardous to your health A terminal bar marked for equipment ground only is located inside the high vol...

Страница 6: ...duction Package Contents The CP3800 T system includes the following components CP 3800 Control Panel w cable 1 qty LX 3800 Power Center 1 qty CVA 24T Valve Actuator 2 qty PTV 2T 3 Port Valve 2 qty SNS...

Страница 7: ...l Cp3800 The CP3800 TL system includes the following components CP 3800 Control Panel w cable 1 qty LX 3800L Power Center 1 qty CVA 24T Valve Actuator 2 qty PTV 2T 3 Port Valve 2 qty SNS KIT2 Sensor K...

Страница 8: ...eturn to the other port 4 Plumb 3 4 spa makeup line incorporating a 3 4 ball valve and a 3 4 check valve During pool circulation some of the pool water needs to enter the spa to keep it chemically bal...

Страница 9: ...ld be used when distance to panels exceeds 200 or panels are elevated higher than 25 11 Glazed solar panels require a drain valve model HW 5B to allow draining of panels This prevents damage from over...

Страница 10: ...the equipment Provide power from the Main panel located at the house to Power Center Power Center without built in Sub panel At the equipment pad mount a 100 amp electrical circuit breaker panel Sub p...

Страница 11: ...er The system draws less than 1 amp Do not use a GFCI circuit breaker 2 Run appropriate wires from the circuit breaker to the System Power terminal block 3 For a 115 volt connection connect to termina...

Страница 12: ...P install an external contactor Use relay to switch coil of external contactor Adding Relays The Power Center comes standard with 4 relays It is possible to add additional relays model RLY LX The LX 3...

Страница 13: ...e light to LOAD 1 of the relay terminal block 5 Connect a wire from LINE 1 of the relay terminal block to the LOAD SIDE of the GFCI receptacle Note The example above assumes the pool or spa light is 5...

Страница 14: ...X7 AUX VLV CNTRL FREEZE I L SYST SPEC FUNCT HISPD SPA POOL HEAT SPA CLNR FDEL SOLR HTPMP MANHT WFAL FLRCL DIM3 DIM4 A7BW A730 SPA HTR AUX1 SOLR PHONE CONTROLS DIMMER 3 DIMMER 4 FLRCL CONTROL JUMPERS C...

Страница 15: ...ance is not long enough it is possible to splice in additional wire to lengthen cable Use 3 conductor wire model 3COND CVA To install Valve Actuators 1 Remove knob handle and four cover screws from th...

Страница 16: ...Center circuit board connect 2 conductor cable to the HTR terminals 4 If heater has electronic ignition provide high voltage power from the Sub panel Water Temperature Sensor The Water Temperature Sen...

Страница 17: ...ment pad To wire the Freeze Temperature Sensor 1 Install the sensor next to the Power Center 2 Run a 2 conductor cable from the sensor to the Power Center 3 At the sensor use crimp connectors included...

Страница 18: ...nts Insert mounting anchors included into the three holes 4 Pull cable through large hole in backplate use the three 1 25 screws to mount backplate to wall Use crimping tool to connect modular connect...

Страница 19: ...ng from an electrical supply store verify it is designed to crimp 6 position connectors To install the modular connectors 1 Use stripper to remove cable jacket 2 Insert modular connector into crimper...

Страница 20: ...c pipe with pvc cement so that the red button will be on top 5 At the Power Center connect Spa side Remote wires to appropriate screw terminals located at bottom of the of the circuit board 6 Connect...

Страница 21: ...model 6COND DUAL is required Valve Module The Valve Module model MOD VLV3 allows the system to control three additional Valve Actuators To install Valve Module 1 Attach Valve Module to the top of the...

Страница 22: ...ed panels fasten sensor next to solar panels For glazed panels suspend sensor between collector and glazing 2 Run a 2 conductor cable from the sensor to the Power Center 3 At the sensor use crimp conn...

Страница 23: ...ct an auxiliary circuit AUX1 AUX7 and connect RLY LXD control wire into the appropriate relay socket Telephone Module The Telephone Module model MOD TELSPA allows turning the spa on off from a phone I...

Страница 24: ...C FNCT configuration switch A7BW located at the bottom of the Power Center circuit board 4 Turn off SPEC FNCT configuration switch A730 5 Program the backwash interval and duration times at the Contro...

Страница 25: ...pump single pump system CLNR Activate cleaner interlocks Cleaner must be installed on AUX1 FDEL Activate filter delay heater cool down SYST System System settings are used to configure the following e...

Страница 26: ...to reverse phase ON1 ON2 3 Press Equipment keys Filter 1 2 3 4 5 6 and 7 verify equipment is being activated 4 Press the Heater key verify heater fires Filter pump must also be on 5 Press the Solar k...

Страница 27: ...as needed Equipment Keys Equipment keys activate the Spa Pool and up to 6 additional items Each key can be custom labeled for your specific application To turn equipment on or off press the appropria...

Страница 28: ...additional 10 minutes to allow the heater to cool down During this cool down cycle and icon on the display will indicate DELAY Some heaters do not require a cool down period so this function may have...

Страница 29: ...o heating For added convenience whenever the spa is manually activated from either the Control Panel or the Spa side Remote the Spa Heat Source Lamp will automatically switch to Heater Turning the spa...

Страница 30: ...ey Located behind the right door of the Control Panel is the Temp Display key Press this key to select Fahrenheit or Celsius temperature display Programming Behind the right door of the Control Panel...

Страница 31: ...y to set the RUN TIME 6 Press the Program key to end Programming additional Run Times It is possible to program up to four separate START TIME and RUN TIME s for each equipment key Follow the previous...

Страница 32: ...w of blinking icons located immediately above the eight Equipment keys 2 Press and hold down the Cancel key for 5 seconds After 5 seconds a continuous alarm will sound until you release the Cancel key...

Страница 33: ...ess the Spa Heat Source key 3 Enter correct pool temperature and press Spa Heat Source key 4 Enter correct solar temperature and press Spa Heat Source key 5 Enter correct air temperature and press Spa...

Страница 34: ...s for calibrating the temperature sensors Water Sensor Let the pool run for 5 minutes to allow water temperature sensor to accurately pickup current pool water temperature Solar Sensor Put a thermomet...

Страница 35: ...the following modes Auto Control Panel and Spa side Remote are enabled Power Center keys are disabled Service Power Center keys are enabled Control Panel and Spa side Remote are disabled A blinking A...

Страница 36: ...s particularly useful when adding chemicals to the pool Note The Control System must be in Auto mode to enable these feature To turn the filter pump on press the P key Filter Pump 2 times quickly The...

Страница 37: ...at Boost feature it is possible to manually activate the heater and boost the spa temperature for a five minute period This feature can only be activated if the Spa side Remote light is not blinking T...

Страница 38: ...ds 2 speed Filter Pump Control The 2 speed filter pump can be switched to high speed under the following conditions Cleaner is on Spa is on Heater is on Solar is on Note When the 2 speed filter is tur...

Страница 39: ...37 Compool Cp3800 Winterizing the System In areas where freezing temperatures occur for an extended period of time it is required to consult a qualified service company to winterize your pool...

Страница 40: ...Sensor model TS 5L Display shows Err 4 If the Control Panel is not able to communicate with the Power Center the display will show Err 4 Check communication cable and connections Use test cable provi...

Страница 41: ...anel Check circuit breakers in the Sub panel and Power Center Check communication cable Clock lost time after power failure Replace battery located on Power Center circuit board System not responding...

Страница 42: ...by someone other than Compool Inc or which have been damaged because of a defect in a component or part which is not part of the Compool Control System or upon which the serial number or manufacture...

Страница 43: ...nt Status Lamps 26 Fahrenheit Celsius key 28 Floor Cleaner Valve 22 FREEZE 23 Freeze Protection 36 Freeze Temperature Sensor 15 Gas Heater Connections 14 Heat Pump or Electric Heater 20 Heater Protect...

Страница 44: ...ime of Day 30 Solar Booster Pump Control 20 Solar Heating 20 Spa Waterfall Control 36 Spa side Heat Boost 35 Spa side Remote 18 Spa side Remote 35 SPEC FUNCT Special Functions 23 SYST System 23 System...

Страница 45: ......