PM1323
TABLE 7-2 SINGLE PHASE INDUCTION MOTOR STARTING REQUIREMENTS.
CODE
Volts = 230 HP = 1/4 using table 8-2; code M = 11.2 KVA / HP
11.2 x 1/4 x 1000
Therefor, starting the motor requires 12.2 Amperes.
EXAM PLE 3:
Calculate the starting amperage required for a 230 V, 1/4 HP motor start code of M
KVA / HP x HP X 1000
VOLTS
= STARTING AMPERAGE.
VOLTS
= 12.2 A.
FIG. 7-3 POW ER REQUIRED TO START MOTOR.
FIG. 7-4 STARTING AMPERAGE CALCULATION
G
KVA/HP
6.3
H
7.1
J
8.0
K
9.0
L
10.0
M
11.2
N
12.5
P
14.0
1.- MOTOR RATING LABEL.
2.- MOTOR START CODE.
Determ ine power required to start motor using
Table 7-2. Determine starting amperage requiered
as shown in Figure 7-4.
3.- RUNNING AMPERAGE REQUIREMENT.
If code is not present, multiply running requirements
by six . Generator amperage output must be at
l east t wic e t he m ot or ' s r unni ng am perage
requirement.
2
1
AC MOTOR
VOLTS 230
AMPS 2.5
CODE
Hz 60
HP 1/4
1 PHASE
3
25
Содержание BRONCO 255K XD
Страница 35: ...PM1323 6 7 21 8 17 15 16 14 18 12 1 2 3 3 3 4 5 19 20 10 9 11 16 13 30...