Responding to Alarms
This section describes the alarms that can be generated by the iPatch Manager, the
possible causes, and how to respond to them.
For each alarm, the possible causes and associated solutions are listed in the order
of likelihood. After you perform the first action in the “You should…” column, press
Menu and, with Run Diagnostics highlighted, press Select. Check to see whether
the alarm is still in the list. If the alarm still exists, perform the next action in the “You
should…” column and run the diagnostic tests again. Continue until the alarm no
longer appears in the list.
You notice this alarm…
Possible causes include…
You should…
Network Manager Not Communicating
a. iPatch Manager selected to communicate
with System Manager (Rack Manager Plus
or Panel Manager with Network Manager
module installed) is not configured
properly.
a. At the iPatch Manager display, make sure that
the iPatch Manager selected to communicate
with System Manager is configured properly.
The Network setting should be set to Off. (For
the Panel Manager with Network Manager
module installed, see page 2–16. For the Rack
Manager Plus, see the
SYSTIMAX
®
iPatch
®
System Rack Manager Plus Guide.)
b. iPatch Manager has failed.
b. Replace the iPatch Manager. (See page 5–8.)
Network Manager Not Found
a. Patch cord connecting the Network
Manager module to the Panel Manager is
loose.
a. Check the patch cord. If it is loose, secure both
ends of the patch cord.
b. Patch cord connecting the Network
Manager module to the Panel Manager has
failed.
b. Disconnect the patch cord and connect a
working patch cord. If the problem is fixed,
replace the failed patch cord.
c. Power adapter is not securely connected
from the Panel Manager with Network
Manager module to the electrical service
outlet.
c. Check to see whether the power adapter is
properly connected to a PWR IN jack on the
back of the Network Manager module and to
the electrical service outlet. If it is not
connected, connect it.
d. Power is not working at one or more of the
electrical service outlets.
d. Check to see whether power is working at the
electrical service outlet. If it is not, restore
power to the electrical service outlet.
e. The Network Manager module has failed.
e. Replace the Network Manager module. (See
.
)
No Panels Found
a. No iPatch Panels are connected to the
panel bus.
a.
If iPatch Panels are installed
, connect the
panels and modules to the panel bus.
If no iPatch Panels are installed
, no response is
necessary.
b. Panel bus jumper connecting the iPatch
Manager to the panel bus is loose, upside
down, or not connected.
b. Check the panel bus jumper. If the jumper is
loose, secure both ends of the jumper. Make
sure the polarized tab on the connector is
inserted into the opening in the header on the
panel bus.
c. A connector on the panel bus was
momentarily shorted during installation.
c. Remove power from the iPatch Manager and
then restore power.
continued