Troubleshooting 

You  notice…

 

Possible causes include…

 

You  should…

 

You attempt to trace a patch 
connection and the rack/panel/ 
port  information does not appear 
on the  imVision Controller display.

 

a.

 

Panel bus jumper connecting the 

panel or shelf to the panel bus is loose 
or upside down.

 

 
 
 
 

 

b.

 

Panel bus jumper connecting the 

panel or module to the panel bus has 
failed.

 

 

 

c.

 

Panel or module is not communicating.

 

 
 

 

d.

 

Port’s button has failed.

 

 
 
 
 

 

e.

 

HD Fiber module is not inserted 
correctly.

 

a.

 

Check the panel bus jumper. If it is loose, secure both ends  of the 

panel bus jumper. Make sure the polarized tab on the  connector is 
inserted into the opening in the header on the  panel bus. Also check 
that panel bus jumper chain is connected all the way back to the main 
panel bus. See instruction manual for details.

 

 

b.

 

Disconnect the panel bus jumper and connect a known working 

panel bus jumper. If the problem is fixed, permanently  replace the 
failed panel bus jumper.

 

 

c.

 

Press a button on the imVision Controller. If the imVision  Controller 

responds, see the troubleshooting information for the  “Panel X (Row 
X) Not Communicating” alarm.

 

 

d.

 

Press the port’s button. If the imVision Controller display  does 

not change, the port’s button has failed. You can use  System 
Manager to mark the port broken”. See the imVision  System 
Manager help topic “Marking Ports and Outlets as  Broken” or 
contact CommScope support.

 

 

e.

 

Verify HD Fiber module is properly seated in the shelf 

backplane.

 

You trace a patch connection and a 
port in the connection is identified 
on  the display with the wrong 
panel or shelf number.

 

The order of iPatch equipment in 
the rack was not programmed 
correctly.

 

Use the Reset Panels feature to reprogram the order of iPatch 
equipment in the rack.

 

You attempt to trace a patch 
connection and the LEDs do not 
turn  on where you expect.

 

a.

 

Patch cord is not connected 

where it is supposed to be.

 

 

 

b.

 

Wrong connection has been 

recorded in the  database.

 

a.

 

Manually trace the patch connection to determine the other  end 

of the connection. Remove the patch cord and reconnect the patch 
cord to the proper ports.

 

b.

 

Use the Trace and Change feature to update the connection.

 

Your administrator just used the 
System Manager Software to 
schedule a job, but the job does 
not appear on the imVision 
Controller display.

 

a.

 

The imVision Controller is not 

communicating with the System 
Manager Software.

 

b.

 

The job was not scheduled as an 
“immediate” job.

 

 

c.

 

iPatch equipment in the equipment 
room is in use.

 

d.

 

System Manager was 

synchronizing its database with an 
equipment room when the job was 
scheduled.

 

 

e.

 

The job is not displayed 

because it cannot be 
performed until another job in 
the job queue is  performed.

 

 

f.

 

System Manager has placed the job 

on hold because  a port to  be used  in 
the  job  is  unavailable  or  there  is  a 
problem at the equipment.

 

a.

 

Check whether there is a red X  ∞ appears on the Ready 

screen. If not see the troubleshooting table entry for this problem.

 

 

b.

 

Contact your System Manager administrator to check the 

scheduling for the job. Only jobs that are scheduled as 
“immediate” will be sent to the rack right away.

 

 

c.

 

Return to the Ready screen at the imVision Controller display.  Do 

not perform any activities until you see “Communicating,  Please 
Wait” and then the Ready screen.

 

 

d.

 

Wait for System Manager to complete the synchronization.  Upon 

completion, it will automatically send the job.

 

 

e.

 

Perform any other jobs in the job queue. The job you are 

waiting for should appear.

 

 

f.

 

Contact your System Manager administrator to check why the job is 

on hold. Then respond to the problem causing the job to be kept on 
hold. See the imVision System Manager help topic “Managing the 
Work Order Queue”

 

 

 

 

 

Содержание SYSTIMAX imVision

Страница 1: ... Instructions 2 The imVision System 3 iPatch Panel 3 imVision Controller 3 Ordering Panels in the imVision System 4 Following Prompts in the imVision System 5 Screen Lock PIN Feature 5 Audible and Visible Feedback 6 imVision System Manager Software 6 Settings 7 Patching Mode 7 Patching and Tracing 7 Performing Guided Patching Jobs 7 Performing Unguided Patching Jobs 8 Tracing a Patch Connection 8 ...

Страница 2: ... product on an unstable cart stand or table The product may fall causing serious damage to the product When installing iPatch equipment not described in this guide follow the instructions provided with that equipment Take care not to compromise the stability of the rack by installation of equipment The touchscreen display is designed to be used without the need for a stylus Never use sharp objects...

Страница 3: ... sensor changes at the iPatch panels By monitoring button presses and sensor changes at the panels the imVision Controller logically infers when patch connections are added or deleted and updates the database accordingly In most configurations multiple imVision Controller units are grouped and connected into patching zones Each patching zone requires a LAN connection in order to communicate with t...

Страница 4: ... the rack and so on Press each button to hear a tone confirming its inclusion in the order until all the panels in the rack are numbered At that point the tone will change and the imVision System will enter the Ready state with the Home screen appearing on the interface If the rack includes a high density fiber shelf or shelves you must also order the modules by pressing a button on each module of...

Страница 5: ...y Screen Lock PIN Feature When enabled the Screen Lock PIN feature locks an imVision Controller display until a PIN is entered on the display number keypad Touch the lock icon on the bottom right corner of display to show a keypad then enter PIN to unlock the display screen Enable the screen lock PIN feature by entering the Controller Settings menu on the Home screen Choose Screen Lock Settings ch...

Страница 6: ...ort beep Pressed controller key Inserted or removed a patch cord at an iPatch Panel Completion tone 3 short tones low medium high Added or removed patch connection at an iPatch Panel Indicated the position of a row of iPatch Panel ports Saved a network setting Confirmation tone 2 short tones Programmed the order of the panels and modules in the rack Attention tone 1 long low tone Technician is req...

Страница 7: ...ormal the imVision Controller shows the patching mode on the Idle screen below the Rack Name The patching mode is set to Normal when the Jobs button is pressed Normal All imVision Controllers in this mode monitor connections simultaneously for a given Controller LAN Local Unless the Jobs button is pressed each imVision Controller monitors only the activity in its own rack creating a local patching...

Страница 8: ...m the iPatch Panel unplug the patch cord from the equipment Then disconnect the patch cord from the panel Press and hold the button above the newly vacated port on the iPatch Panel for 2 seconds This will confirm that the unguided equipment patch removal has been completed Tracing a Patch Connection When you connect a patch cord to an iPatch Panel the system records the connection in a database To...

Страница 9: ...ced port Step 3 Confirm the correct connection for each port After using the Change button the imVision Controller will automatically step through each port that was involved in the changed connection For each port a Confirm screen will appear to provide guidance for confirming the connection information Follow the on screen instructions to create a new connection relationship between ports or wit...

Страница 10: ...t the patch connection you want to confirm Then either Press and hold the port button in the panel directly above the port where the other end of the cord is inserted and confirm on the display that the connection is complete or If the other end of the patch cord is hanging free plug in the cord and answer Yes to the question Insert one end of the patch cord and press and hold the button on the pa...

Страница 11: ...ther the B or A strand is the far end of the patch being confirmed When the correct connection is displayed press Yes Complete the connection to equipment Press and hold the iPatch panel port s button for 2 seconds or press the Equipment button on the imVision Controller display Remove the connection Remove both ends of the patch cord Connecting Controllers in a Zone A zone is a group of racks and...

Страница 12: ...ed if the port is used to connect from the imVision Controller to another controller in the zone The Controller mode is selected when the button next to a port is in the pushed out position When pushed out the button is flush with the controller housing The example above shows the patch cord connections and button positions required to configure a zone containing three imVision Controllers ...

Страница 13: ...rder ofiPatch equipment in the rack You attempt to trace a patch connection and the LEDs do not turn on where you expect a Patch cord is not connected where it is supposed to be b Wrong connection has been recorded in the database a Manually trace the patch connection to determine the other end of the connection Remove the patch cord and reconnect the patch cord to the proper ports b Use the Trace...

Страница 14: ...roperly for the current patching b imVision Controller is not connected to the adjacent imVision controller c imVision Controller has failed d imVision Controller is not responding e Panel or module is not communicating with the imVisionController f Patch cord connecting an imVision Controller to an adjacent controller failed a At each imVision controller press Home to view the controller configur...

Страница 15: ... a The Controller in question has lost power b The Controller in question is improperly connected to the other controllers in the patching zone c The Controller in question does not have its IN and OUT port switches configured correctly d The Controller has been removed from the patching zone in question e The Controller in question has failed a Make sure the Controller is properly connected to it...

Отзывы: