Ruckus ICX 7750 Switch Hardware Installation Guide
Part Number: 53-1003900-10
Installing the Ruckus ICX 7750
Installing the 1U, 1.5U, and 2U Universal Kit for Four-Post Racks (XBR-R000295)
3.
Attach the left front bracket to the left front rack post using two 10-32 x 5/8-in. panhead screws and two retainer nuts. Use the
upper and lower holes in the bracket.
4.
Tighten all the 10-32 x 5/8-in. screws to a torque of 25 in-lb (29 cm-kg).
FIGURE 17
Positioning the device in the rack
Attaching the rear brackets to the extensions
Complete the following steps to attach the rear brackets to the extensions. There are short and long rear brackets that you can use for this
step. Choose the correct bracket for the depth of your rack.
1.
Select the proper length rear bracket for your rack depth.
2.
Slide the right rear bracket onto the right extension, as shown in
.
The short rear brackets are shown. Use the first and third vertical pairs of holes for the screws.
Refer to
for the positioning of the medium or long brackets and screws.
3.
Attach the brackets using four 6-32 x 1/4-in. panhead screws.
4.
Repeat step 2 and step 3 to attach the left rear bracket to the left extension.
5.
Adjust the brackets to the rack depth and tighten all the 6-32 x 1/4-in. screws to a torque of 9 in-lb (10 cm-kg).
1
Screws, 10-32 x 5/8-in., panhead Phillips
2
Retainer nuts, 10-32